Bosch Appliances F220-B6 Test Each Detector, Activate an Alarm at Each Detector

Models: F220-B6

1 28
Download 28 pages 11.75 Kb
Page 24
Image 24

24 en Test the Installation

F220 Series Detectors with F220-B6/C/E/R Bases

 

 

every eight seconds. This verifies the detector is receiving power and operating properly.

NOTE! If a heat detector LED flashes at a rate of

4 flashes/sec, the detector is either cold (below +32°F

i [0°C]), out of sensitivity range, or defective. If a smoke detector flashes at a rate of 4 flashes/sec, it is either out of sensitivity range or defective.

5.2Test Each Detector

Test each detector to ensure it causes a control panel alarm. Reset the control panel after each test.

5.2.1Activate an Alarm at Each Detector

To cause heat detectors to alarm either:

Activate the internal reed switch by placing a magnet horizontally against the T mark on the mounting skirt (refer to Figure 4.2, Item 8 on page 19) and holding it there for three consecutive LED flashes, or

Expose the thermistor (refer to Figure 2.2, Item 3 on page 7)to a heat source such as a hair dryer or a shielded

heat lamp until the detector alarms and the alarm LED lights .

To cause smoke detectors to alarm either:

Activate the internal reed switch by placing a magnet horizontally against the T mark on the mounting skirt (refer to Figure 4.2, Item 8 on page 19) and holding it there for three consecutive LED flashes, or

Use a UL Listed aerosol smoke detector tester to simulate an alarm. Follow the instructions provided with the aerosol smoke detector tester.

5.2.2Reset the Control Panel

When a detector alarms, the red LED indicator activates and latches into the ON position. Clear the alarm by momentarily removing power before proceeding to the next detector.

4998138694 -04 2007.01

Installation Manual

Bosch Security Systems, Inc.

Page 24
Image 24
Bosch Appliances F220-B6 Test Each Detector, Activate an Alarm at Each Detector, Reset the Control Panel