| 9.0 | Troubleshooting |
|
|
|
9.0 Troubleshooting
Refer to Table 2 when troubleshooting the
Table 2: FMR-7036 Troubleshooting Tips
Keypad Notification | Possible Causes |
Continuous keypad sounder | The yellow and green wires |
PLUS ""System Fault"" | have been disconnected. |
display | The keypad has not been |
| programmed at the control |
| panel. The control panel has |
| malfunctioned. |
Control panel does not | The keyswitch is in LOCK |
respond to keypad input. | position. The keypad's |
| address has not been set |
| with the jumper pins. |
10.0 Specifications
Table 3: FMR-7036 Specifications
Operating Voltage | 12 VDC Nominal from Option |
| Bus |
Normal Standby | 80 mA |
Current |
|
Alarm Current | 100 mA |
|
|
Base Height | 4.1 in (11.6 cm) |
Base Width | 8.2 in (20.8 cm) |
|
|
Cover Height | 4.3 in (10.9 cm) |
Cover Width | 8.1 in (20.6 cm) |
|
|
Environment | Use Indoor/Dry |
Operating Temperature | +32° to 120°F (0° to +49°C) |
|
|
Relative Humidity | 93% |
Listings | UL864, FM |
|
|
Wiring | Supervised Communication |
| Circuit |
Bosch Security Systems, Inc. 9/08 | 7 |