Bosch Appliances GWH-345/450-ESR-N Recommended exhaust vent terminator position, Description

Models: GWH-345/450-ESR-L GWH-345/450-ESR-N

1 40
Download 40 pages 52.3 Kb
Page 21
Image 21
Recommended exhaust vent terminator position

Installation instructions

Recommended exhaust vent terminator position

Fig. 21

Ref.

Description

Minimum distance

 

 

 

A

Directly below an opening; operable windows, doors and any non-

36 in (twin pipe installation)

mechanical fresh air openings

48 in (single pipe installation)

 

 

 

 

 

Below a gutter, sanitary pipework or eaves

24 in

B

Below a gutter, sanitary pipework or eaves, protected by metal

12 in

 

shielding

 

 

 

 

 

C

From any internal corner

12 in

D*

Above ground or snow pack

12 in

 

 

Above a paved sidewalk

7 ft

 

E

From an opposing wall or structure facing the termination

24 in

 

 

From the relief valve of a Ip gas regulator

36 in

 

F

From a terminator facing a terminator

48 in

G

Vertically between two exhaust vent terminators on the same wall

60 in

 

 

 

H

Horizontally between two exhaust vent terminators on the same wall

12 in

 

 

 

 

Horizontally and vertically from the combustion air inlet terminator

36 in

I**

 

 

 

 

 

 

 

From the gravity combustion air inlet any other equipment

48 in

J

From any external corner

12 in

K

Horizontally from an opening; operable windows, doors and any non-

12 in

mechanical fresh air openings

 

 

 

 

 

L

From wall on exhaust applications

10 in

 

 

 

Table 10

* Subject to local codes and anticipated snow level

** Other equipment that operates with a mechanical air inlet may require greater distances, reference manufacturer's instructions

NOTICE: Exhaust and air intake must always be located on the same wall to cancel wind pressure effects.

6 720 607 909

21

Page 21
Image 21
Bosch Appliances GWH-345/450-ESR-N Recommended exhaust vent terminator position, Installation instructions, Description