Figure 15. Control Parameter Graph.

25% and 100% of full fire between 46°C and 49°C. Between 46°C and 49°C, the unit will remain at low fire. Between 38°C and 41°C, the unit will be at full fire.

The throttling range is adjustable between 2°F and 30°F (1°C to 17°C). The range can be set by removing the cover of the S350P control and adjusting the “THROT RANGE” dial (see Figure 14).

5.5.5Minimum Output Setting

The minimum output setting of the controller is 0% of full fire. However, the minimum output of the Brute Magnum is limited to 25% of full fire by the fan speed controller, to ensure proper operation of the Brute Magnum. If a minimum desired output is higher than 25%, the setting can be adjusted up by removing the cover of the S350P control and adjusting the Min Output dial (see Figure 14). Turning the dial clockwise increases the minimum output. In most cases, this setting should be left as shipped from the factory.

5.5.6Integration Constant

The proportional control used on the Brute Magnum has internal circuitry that helps to minimize overshoot that can sometimes be associated with proportional plus integral (PI) controls. There

are three field-selectable integration constants (slow, medium and fast), and an off position on the proportional control, which are selected with the dipswitches on the control (see Figure 14). In most cases, this setting will not need to be changed

Off: Switch 1 to ON position and all others to OFF. Setting the control to the “Off” position puts the control into proportional only operation. This is not a recommended setting for the Brute Magnum.

Slow: Switch 2 to ON position and all others to OFF. This is the slowest integration constant. It allows the Brute Magnum the most time to reach its setpoint. In most cases, this is too slow for Brute Magnum installations.

Medium: Switch 3 to ON position and all others to OFF. The integration constant is set to “Medium” at the factory, and in most cases, will not need to be