(13)Revision

2 = Second version

(14)Heat Exchanger

E = Glass-lined steel with copper tubes

F = Glass-lined steel with cupronickel tubes

(15)Control Option Code

X = Standard, meets CSD-1 boiler standard A = Control Pack A: CSD-1, CA, FM, IL, IRI,

Alarm Bell

B = Control Pack B: CSD-1, CA, FM, IL, LDS, MN F = Non CSD-1

(16)Pump Options

N = Pump mounted, normal pump (standard) H = Pump mounted, hard water pump (BRHHV)

1.3Warranty

Bradford White’s Brute Magnum appliances

are covered by a limited warranty. The owner should fill out the warranty registration card and return it to Bradford White.

All warranty claims must be made to an authorized Bradford White representative or directly to the factory. Claims must include the serial number and model (this information can be found on the rating plate), installation date, and name of the installer. Shipping costs are not included in the warranty coverage.

Some accessory items are shipped in separate packages. Verify receipt of all packages listed on the packing slip. Inspect everything for damage immediately upon delivery, and advise the carrier of any shortages or damage. Any such claims should be filed with the carrier. The carrier, not the shipper, is responsible for shortages and damage to the shipment whether visible or concealed.

1.4Dimensions

The overall dimensions are 34.5" (88cm)

wide, 65.75" (167cm) tall, 55" (140cm) deep. Other dimensions can be found in Figure 1.

1.5Locating the Appliance

The Brute Magnum is for indoor installations

only.

The appliance should be located to provide clearances on all sides for maintenance and inspection. It should not be located in an area where leakage of any connections will result in damage to the area adjacent to the appliance or to lower floors of the structure.

When such a location is not available, it is recommended that a suitable drain pan, adequately drained, be installed under the appliance.

The appliance is design certified by CSA- International for installation on combustible flooring; in basements; in closets, utility rooms or alcoves.

Brute Magnum Boilers or Water Heaters must never be installed on carpeting. The location for the

appliance should be chosen with regard to the vent pipe lengths and external plumbing. The unit shall be installed such that the gas ignition system components are protected from water (dripping, spraying, rain, etc.) during operation and service (circulator replacement, control replacement, etc.). When vented vertically, the Brute Magnum must be located as close as practical to a chimney or gas vent. If the vent terminal and/

or combustion air terminal terminate through a wall, and there is potential for snow accumulation in the local area, both terminals should be installed at an appropriate level above grade.

The dimensions and requirements that are shown in Table 1 should be met when choosing the locations for the appliance:

Appliance

Clearance From

Suggested Service

Surface

Combustible Material

Clearance

 

inches

inches

Piping Side

1

18

Opposite Side

1

1

Top

1

24

Back

1

36

Front

1

36

Vent

per UL1738 venting

 

 

system supplier’s

 

 

instructions

 

Table 1. Clearances.

1.6 Locating Pump-Mounted Water Heater with Respect to Storage Tank(s)

For best results the Brute Magnum water heater should be located within 15 feet (4.6m) of the storage tank(s). The pump is sized for 30 feet (9.1m) of piping.

Water heater pumps are sized for water hardness;

7.6to 17 grains per gallon for normal water, greater than 17 grains per gallon for hard water, and 1 to

7.5grains per gallon for soft water. If the appliance must be installed with longer piping runs, then larger diameter pipe or tubing may be able to be used, in some instances. Consult the factory for assistance.

1.7 Locating Pump-Mounted Boiler with Respect to Return/Supply Header

Brute Magnum units must be piped in primary- secondary fashion because of the internal pump and mixing system.

For the best results the Brute Magnum Boiler should be located within 15 feet (4.6m) of the supply and return headers. The pump is sized for 30 feet (9.1m) of piping, in most cases, enough for primary- secondary piping systems.

If the appliance must be installed with longer piping runs, then larger diameter tubing may be able to be used, in some instances. Consult the factory for assistance.