Briggs & Stratton Power Products Automatic Transfer Switch
Installation and Operator’s Manual
TROUBLESHOOTING
Problem | Cause | Correction | |||
Automatic transfer switch does | 1. | Generator breaker open. | 1. | Reset generator circuit breaker. | |
not transfer to generator | 2. | Generator voltage not acceptable. | 2. | Refer to generator manual. | |
|
|
|
|
| |
| 1. | Utility disconnect breaker open | 1. | Reset utility disconnect breaker | |
Automatic transfer switch does |
| (Models |
| (Models | |
2. | Service disconnect breaker open. | 2. | Reset service disconnect breaker. | ||
not transfer to utility | |||||
3. | Utility voltage not acceptable. | 3. | Wait for utility voltage to return to | ||
| |||||
|
|
|
| normal. | |
|
|
| |||
Generator is still running after | Engine cool down period. | Engine should stop after 1 minute. | |||
switch transfers to utility power |
|
|
|
| |
|
|
| |||
Supervised loads (air conditioner, | NC contacts not operating correctly. | Check NC contacts for proper | |||
etc.) are operating when |
|
| operation and/or check control wiring | ||
generator is supplying power |
|
| to external load. | ||
|
|
|
|
| |
| 1. | Minimum engine run time has not | 1. | Wait five minutes for transfer | |
Generator is still running after |
| elapsed. |
| switch to retransfer to utility | |
|
|
| power. | ||
utility power is restored |
|
|
| ||
2. | Fuse(s) in transfer switch is | 2. | Check fuse(s) and replace if | ||
| |||||
|
| defective. |
| necessary. | |
|
|
|
|
|
12