Briggs & Stratton 01928-1 Troubleshooting, Problem, Cause, Correction, not transfer to generator

Models: 01813-1 01928-1 01814-1 01929-1

1 44
Download 44 pages 13.59 Kb
Page 12
Image 12
TROUBLESHOOTING

Briggs & Stratton Power Products Automatic Transfer Switch

Installation and Operator’s Manual

TROUBLESHOOTING

Problem

Cause

Correction

Automatic transfer switch does

1.

Generator breaker open.

1.

Reset generator circuit breaker.

not transfer to generator

2.

Generator voltage not acceptable.

2.

Refer to generator manual.

 

 

 

 

 

 

1.

Utility disconnect breaker open

1.

Reset utility disconnect breaker

Automatic transfer switch does

 

(Models 01928-1 & 01929-1 only).

 

(Models 01928-1 & 01929-1 only).

2.

Service disconnect breaker open.

2.

Reset service disconnect breaker.

not transfer to utility

3.

Utility voltage not acceptable.

3.

Wait for utility voltage to return to

 

 

 

 

 

normal.

 

 

 

Generator is still running after

Engine cool down period.

Engine should stop after 1 minute.

switch transfers to utility power

 

 

 

 

 

 

 

Supervised loads (air conditioner,

NC contacts not operating correctly.

Check NC contacts for proper

etc.) are operating when

 

 

operation and/or check control wiring

generator is supplying power

 

 

to external load.

 

 

 

 

 

 

1.

Minimum engine run time has not

1.

Wait five minutes for transfer

Generator is still running after

 

elapsed.

 

switch to retransfer to utility

 

 

 

power.

utility power is restored

 

 

 

2.

Fuse(s) in transfer switch is

2.

Check fuse(s) and replace if

 

 

 

defective.

 

necessary.

 

 

 

 

 