Meter Set To Read DC Volts
These tests assume that the CommLink II is connected and powered, and that all MiniLinks which are connected are also powered.

WattMaster WHP

Section 4

 

 

5.3.4Checking the MiniLink Network Loop

Diagram

Meter Set To Read DC Volts

The indicated readings are typical of a normally operating system. Actual readings may vary slightly due to the number of units installed and other factors. Any significant devia- tion from these values generally indicates a problem.

Note:Overview

Proper loop voltages are essential for reliable communications. It is normal to see fluctua- tions on an operating communications loop. The average value should be close to the ac- ceptable range described below. Values will vary upon initial powerup for about 15-30 seconds as normal communications occur.

Measurements

 

 

 

 

 

 

 

 

LOCALT - G (SHLD)LOOP

2.9 - 3.1 Volts DC

AcceptableRange

 

 

 

 

 

 

 

 

R - G (SHLD)

1.9 - 2.1 Volts DC

 

 

 

 

 

 

 

 

 

 

 

 

Action

 

 

 

 

 

 

 

 

 

 

Readings near ZeroConditionVolts

 

Check for shortedActionwiring.

 

 

 

 

 

 

If voltages are too high or too low on either

 

1.

One or more devices connected to this

 

side

 

 

 

loop may have damaged Comm driver

 

 

 

 

 

chips.

 

 

 

 

2.

Wiring errors. Check for multiple loops

 

 

 

 

 

“cross connected”, short circuits, etc.

 

 

 

 

 

 

 

Start-Up and Troubleshooting

4-27