WHPoopSetpoints

Section 3

WattMaster WHP

 

 

Setpoint Screen #9

WHPoopSetpoints

 

The two pumps will switch after this programmed amount of

 

same time.

 

 

 

 

 

time so that each pump accumulates roughly the same

Lead/LagChangeover

 

 

 

 

 

 

number of run time hours. If a

pump is currently

running and

SwitchAfterxxxHrs

 

 

 

this time period is exceeded, the

changeover will occur as

 

 

soon as pump run time exceeds

the setpoint. The current

 

 

pump will shut off and the standby pump will start at the

 

 

Changeover

Minimum1 Hour

40DefaultHours

Maximum240 Hours

Setpoint Screen #10

WHP

Setpints

 

If you attached a Pressure Sensor for proof of flow instead of a

 

appear.

 

 

 

 

 

 

 

 

 

 

 

WaterLoopo

ProofOf

differential pressure contact closure for proof of flow, the

FlowPr.SP:xxxPSI

Flow PR. SP

Minimum0

Default5 PSI

Maximum50 PSI

 

 

 

controlling pressure

is programmed on this

screen. This

Setpoint represents the amount of pressure that you set to prove water flow exists in the system. Otherwise, this screen will not

Setpoint Screen #11

If you configured the system for Variable Speed Pumping with a Pressure Sensor for proof of flow, the controlling pressure, deadband and control adjust time period are programmed on

PresureWHPSPAdjuDeadbandsLooptTimeSP:Setpointsxxx.PSISec this screen. Otherwise, this screen will not appear.

 

 

 

 

 

Pressure SP

Minimum1 PSI

 

Default40 PSI

Maximum50 PSI

SP Deadband

1 PSI

 

2 PSI

50 PSI

Adjust Time

0.1 Seconds

 

1.0 Seconds

25 Seconds

3-30

Programming

Page 78