Setpoints

WattMaster WHPSection 3

Setpoint Screen #11

 

WHP#1

 

 

 

If your system is configured to use the reversing valve and

 

 

 

 

you only have one stage of heating and cooling, that last

 

Relay5Configuratin

 

 

 

relay becomes available for other uses. The AUXILIARY

 

 

 

 

 

 

AUXIIARYRELAYMODE

 

RELAY MODE can be used to operate the relay manually

 

 

from the Prism computer front end program. If you select

 

 

ISOLATION VALVE MODE, the relay activates anytime

 

 

the compressor is called for or whenever the Loop Controller

 

 

sends an override command to activate and reduce loop

 

 

pressure.

 

 

If the relay needs to follow an external week schedule, select

 

UseLeft/RightSetpointsArrw

 

the AUXILIARY RELAY MODE and then see the Aux

 

 

 

 

 

Relay #5 Schedule assignment screen.

Setpoint Screen #12

 

 

 

 

 

You can program the fan to run continuously during the

 

WHP#1

Setpoints

 

 

 

occupied mode, (RUNS CONTINUOUS MODE) or you

 

RUNSCONTINUOUSMODE

 

 

 

can program it to cycle on and off with the compressor

 

 

 

 

 

 

 

 

 

 

during both the occupied and the unoccupied mode of

 

 

 

 

 

operation.

 

 

 

 

 

(CYCLES W/COMPRESSOR)

Setpoint Screen #13

 

FanModeofOp

 

 

 

 

UseLeft/RightArrow

 

If you configured relay #5 as an Auxiliary Relay, you can

 

 

 

also program it to follow an external schedule command.

 

AuxRlay#5Uses

 

 

 

 

0)NonSchedule1-7)Clock

 

 

 

Uses

#:x

 

You must have an OSS Optimal Start Scheduler installed

 

WHP1#

Setpoints

 

somewhere on you communications loop to provide the

 

 

external schedule you select here.

Programming

3-17

Page 65
Image 65
Heat Controller Water Source Heat Pump manual WHP1#, Setpoints, Uses, Cycles W/Compressor