WattMaster WHP | Section 4 |
|
|
3.2.3Binary Output
R1 – Compressor Enable – Energizes the first stage of cooling.
R2 – Main Pump – Energizes the lead water pump.
R3 – Standby Pump – Energizes the standby pump if the main pump fails to start.
R4 – Alarm Indicator – Energizes when an alarm occurs on the Loop Controller.
R5 – Not Used – This output is not used.
COM
COM
3.2.4Relay Expansion Board - Outputs
This connector carries the output relay dry contact open/closed signal.
Relays
Relays
3.2.5Analog Input Expansion Board
The following inputs use dry contact open/closed signals.
AIN1 – Fire Alarm Contact - Used to shut down all equipment in case of a smoke or fire condition.
AIN2 - Request to Run - Used to initiate system start when a water source heat pump controller other than the WattMaster WHP Controller is used.
Warning: Fire Alarm Contact input must be connected to the AIN1- GND terminal if it is not used, a jumper must be connected between AIN1 and GND, since this is a normally closed contact input. If this is not done the system will not operate.