"1.3.11Comm Driver Chip Replacement”.

WattMaster WHP

Section 4

 

 

5.4.4Checking WHP Loop Controller Driver Chip

Diagram

Meter Set To Read DC Volts

These tests assume that the controller being checked is powered up.

Note:Overview

This check is intended to determine if the Comm Driver chip on a controller is damaged. Damage typically occurs when the communications loop is exposed to excessive voltage, as may occur during installation, due to wiring errors. The driver chips are socketed on all boards to facilitate servicing. It is unusual for driver chips to fail during normal operation. Almost all failures occur as a result of wiring related problems.

Measurements

 

 

 

TLocal– SHLDLoop

2.4 - 2.5 Volts DC

AcceptableRange

 

 

 

R – SHLD

2.4 - 2.5 Volts DC

 

 

 

 

Minor variances may not indicate a problem if both tests indicate similar values.

Action

 

 

If voltages are tooConditionhigh or too low on either

The controller hasActiona damaged Comm

side

Driver chip. Replace the driver chip. See

Note:

"1.3.11Comm Driver Chip Replacement”.

 

Start-Up and Troubleshooting

4-39

Page 121