WattMaster WHP | Section 4 |
|
|
5.4Troubleshooting Loop Controller
5.4.1Checking the Loop Controller Analog Inputs
Diagram
Overview
SET METER TO
READ DC VOLTS
+
- | + |
|
-
ALL READINGS ARE TAKEN
WITH THE
METER ON THE GND
TERMINAL
Measurements
Meter
AIN1
Return Water Temp
AIN2
Supply Water Temp
AIN3
Proof of Flow
| The analog input wiring can be checked at the | |
| Loop Controller by checking voltages on the | |
| Analog Input Connector. | |
| If any of the RWT, SWT, OAT inputs read | |
| greater than 5.0 volts then it is OPEN (no | |
12V | sensor is connected), an input that reads less | |
than 0.1 volts is SHORTED. Check for wiring | ||
AIN1 | ||
AIN2 | problems before proceeding. | |
AIN3 | ||
AIN4 |
| |
AIN5 | The Loop Pressure, Manual Reset, Phase | |
GND | ||
GND | Loss, Fire Alarm and Request to Run inputs | |
| ||
AOUT1 | should read greater than 5.0 volts if the at- | |
AOUT2 | ||
AIN7 | tached contact is OPEN and less than 0.5 volts | |
GND | ||
| if the contact is CLOSED (contacts CLOSE | |
| between the input and GND). The Fire Alarm | |
| and Request to Run contacts are located on | |
| the Analog Input Expansion Board. | |
|
| |
|
|
Ignore readings for NoteanyAcceptableconnectionsRangewhich are not used in the equipment.
1.9 volts (100°F) - 3.6 volts (40°F) Typical is 2.5 volts @ 77°F
1.9 volts (100°F) - 3.6 volts (40°F) Typical is 2.5 volts @ 77°F
When used with the Low Pressure Switch option:
If the input is OPEN, the voltage will be greater than 5.0 volts
If the input is CLOSED, the voltage will be less than 0.5 volts
When used with
5.1 VDC = 50 PSI – 0.0 VDC = 0 PSI
|