Room Sensors

WattMaster WHP

Section 2

 

 

Room Sensors

The room sensor uses a patented flush mount design to isolate the temperature sensing element from the housing which mounts flush with the wall surface.

Room sensors should be located on an inside wall away from direct sunlight or heat producing equipment such as computers, copiers, etc. Such devices can adversely affect the accuracy of the sensor.

Although the sensor eliminates most of the effects of thermal coupling to the walls, try to avoid walls which retain large amounts of thermal energy (such as marble or steel). Walls containing either cold or warm air currents should also be avoided whenever possible.

Avoid locating the sensor in dead air areas of a room. This will result in slow response to temperature changes in the space.

Mount the sensor approximately 50-60 inches from the floor for best results.

The room sensor is designed to mounted vertically in a standard 2 by 4 inch electrical box. The sensor may be mounted directly into the drywall where electrical codes do not require low voltage wiring to be enclosed in conduit. See enclosed sheet for dimensional and installation data.

Tip: Be careful when cutting the hole for the sensor or the plastic bezel of the sensor may not completely cover the opening.

WHP CONTROLLER

ROOM SENSOR WITH OVERRIDE

AND ADJUSTABLE SETPOINT

 

TMP

 

 

W

 

1V2

 

A

 

 

 

R

GND

 

 

M

 

 

E

 

 

R

AUX

 

 

C

 

 

O

 

 

 

OVR O

 

 

 

L

 

 

 

E

 

 

 

R

 

 

 

 

ADJUSTABLE

AINGD5431

 

 

SETPOINT

 

 

 

 

PRESURE

S

 

OVERRIDE

SENSOR

 

ONLY REQUIRED WHEN

OUT

 

 

USING ADJUSTABLE

 

Room Sensor Wiring

SETPOINT

 

Figure2-14:

 

 

2-19
Installation and Wiring

 

 