WattMaster WHP | Section 3 |
|
|
Loop Controller Setpoints
Loop Controller Setpoint Menu
| Setpoints |
|
|
|
|
|
|
| |
LC | chedule |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| ||
Setpoint Screen #1 |
|
|
|
|
| ||||
|
|
| If the controlling water temperature rises above this Setpoint, | ||||||
ESC) | ToForceExitModes | ||||||||
2WPHEATLoopREJECTIONSetpoints° |
| the Heat Rejection or Cooling Stages begin to stage on. As the | |||||||
1)3S | :xx°F |
| temperature continues to rise | above the | Setpoint by the | ||||
tageDeadband |
| Deadband amount, an additional stage is added. Each | |||||||
|
|
| |||||||
|
|
| additional stage can only activate if the temperature rises above | ||||||
|
|
| the Setpoint by the number of active stages times the deadband | ||||||
|
|
| value. |
|
|
|
|
| |
|
|
| Example: There are 2 stages on, a 3° deadband and the setpoint | ||||||
|
|
| is 79° |
|
|
|
|
| |
etpoint |
| 2 x 3° + 79° = 85° before stage 3 can activate | |||||||
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| |
|
|
| Setpoint | Minimum50°F |
| Default79°F |
| Maximum99°F | |
|
|
| Stage Deadband | 1°F |
| 3°F |
| 10°F |
Setpoint Screen #2
StageWHPHEATLoopDelayREJECTIONSetpoints...:xM
The Staging Delay period must also be satisfied before an additional stage of cooling or heat rejection can be activated. The maximum number of heat rejection stages are programmed on this screen also.
|
|
|
|
Stage Delay | Minimum1 Minute | 1DefaultMinute | 60MaximumMinutes |
Programming |