Loop Controller Setpoints

WattMaster WHP

Section 3

 

 

Loop Controller Setpoints

Loop Controller Setpoint Menu

 

Setpoints

 

 

 

 

 

 

 

LC

chedule

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setpoint Screen #1

 

 

 

 

 

 

 

 

If the controlling water temperature rises above this Setpoint,

ESC)

ToForceExitModes

2WPHEATLoopREJECTIONSetpoints°

 

the Heat Rejection or Cooling Stages begin to stage on. As the

1)3S

:xx°F

 

temperature continues to rise

above the

Setpoint by the

tageDeadband

 

Deadband amount, an additional stage is added. Each

 

 

 

 

 

 

additional stage can only activate if the temperature rises above

 

 

 

the Setpoint by the number of active stages times the deadband

 

 

 

value.

 

 

 

 

 

 

 

 

Example: There are 2 stages on, a 3° deadband and the setpoint

 

 

 

is 79°

 

 

 

 

 

etpoint

 

2 x 3° + 79° = 85° before stage 3 can activate

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setpoint

Minimum50°F

 

Default79°F

 

Maximum99°F

 

 

 

Stage Deadband

1°F

 

3°F

 

10°F

Setpoint Screen #2

StageWHPHEATLoopDelayREJECTIONSetpoints...:xM

The Staging Delay period must also be satisfied before an additional stage of cooling or heat rejection can be activated. The maximum number of heat rejection stages are programmed on this screen also.

 

 

 

 

Stage Delay

Minimum1 Minute

1DefaultMinute

60MaximumMinutes

Programming

3-27

Page 75
Image 75