Heat Controller Water Source Heat Pump manual 4.0Start-Up, PriorityLowest, No.of1Blinks

Models: Water Source Heat Pump

1 126
Download 126 pages 9.48 Kb
Page 96
Image 96
4.0Start-Up

WattMaster WHP

Section 4

 

 

4.0Start-Up

4.1Blink Codes for WHP Controllers

The WHP Controller uses an on board LED to indicate various diagnostic conditions during powerup and operation. The WHP Unit LED is labeled “COMM”. Starting with power up the LED blink codes are as follows:

Off for five seconds

COMM LED blinks the board address (Address 14 = 14 blinks)

Five second pause

Twenty second time delay - LED blinks twenty times

Status code is repeatedly blinked every ten seconds to indicate controller status:

 

 

 

 

 

PriorityLowest

No.of1Blinks

 

NormalStatusOperation

-

2

 

 

Override Active

-

3

 

 

Bad Space Sensor

-

4

 

 

Heat Pump Lockout

Highest

5

 

 

Communication Failure

Figure 4-6:Diagnostic LED

Codes

 

Only the highest priority failure code will be shown. You must correct the highest priority alarm before other problems will be indicated.

4-14

Start-Up and Troubleshooting

Page 96
Image 96
Heat Controller Water Source Heat Pump manual 4.0Start-Up, PriorityLowest, 4.1Blink Codes for WHP Controllers, No.of1Blinks