Section 3 | WattMaster WHP |
|
|
View Alarms
Alarm Address Locations
| The System Manager can be programmed to poll all the | |
| units on your heat pump system for alarm information. This | |
| allows the centrally located System Manager to display an | |
| Alarm Indicator whenever an alarm condition exists | |
SYSTEMALARMSTATUS | ||
anywhere on your system. The actual alarms are not | ||
displayed on this screen, only the Unit ID where the alarm | ||
is located. The example screen shows that a unit at location | ||
118 has experienced an alarm condition. This alarm may or | ||
may not be current, as the System Manager latches the | ||
Alarm@UnitID118 | condition. This makes it possible to determine if any | |
| intermittent alarm conditions have occured. To find out | |
| what the alarm is, if it is still current, access the status | |
| screens for the Unit IDs that are displayed on the SYSTEM | |
| ALARM STATUS screens. |
Alarm Clearing
UseToClearSYSTEMLeft/RightChangeAlarms?ALAMesponseSTATUSArrowYE
If all the alarm conditions have been corrected at the individual units, you can clear these alarms from the System Manager on the following screen. Use the Left/Right arrow keys to select the YES/NO response desired. If you clear the alarms, but some still exist, the System Manager will show an alarm indication, when the affected unit is polled again.
Programming |