View Alarms

Alarm Address Locations

 

The System Manager can be programmed to poll all the

 

units on your heat pump system for alarm information. This

 

allows the centrally located System Manager to display an

 

Alarm Indicator whenever an alarm condition exists

SYSTEMALARMSTATUS

anywhere on your system. The actual alarms are not

displayed on this screen, only the Unit ID where the alarm

is located. The example screen shows that a unit at location

118 has experienced an alarm condition. This alarm may or

may not be current, as the System Manager latches the

Alarm@UnitID118

condition. This makes it possible to determine if any

 

intermittent alarm conditions have occured. To find out

 

what the alarm is, if it is still current, access the status

 

screens for the Unit IDs that are displayed on the SYSTEM

 

ALARM STATUS screens.

Alarm Clearing

UseToClearSYSTEMLeft/RightChangeAlarms?ALAMesponseSTATUSArrowYE

If all the alarm conditions have been corrected at the individual units, you can clear these alarms from the System Manager on the following screen. Use the Left/Right arrow keys to select the YES/NO response desired. If you clear the alarms, but some still exist, the System Manager will show an alarm indication, when the affected unit is polled again.