Heat Controller Water Source Heat Pump TLocal– SHLDLoop, AcceptableRange, WattMaster WHP, Section

Models: Water Source Heat Pump

1 126
Download 126 pages 9.48 Kb
Page 112
Image 112
TLocal– SHLDLoop
Be sure that the loop you are testing does not have a short circuit from T - R.

WattMaster WHP

Section 4

 

 

5.3.7Checking the Local Loop at MiniLink

Diagram

Meter Set To Read DC Volts

The indicated values are typical of a normal system. Actual readings may deviate slightly due to the number of units connected and other system specific factors

These tests assume that the controllers being checked are powered up.

Note:Overview

This is a “quick check” to determine if any of the WHP Controllers or WHP Loop Control- ler on a Local Communications Loop are damaged. Since all WHP Controllers will “float” both of their communications connections at about 2.45 Volts, you can quickly check an entire loop by unplugging it at the MiniLink.

Note:

 

 

 

 

 

TLocal– SHLDLoop

2.4 - 2.5 Volts DC

AcceptableRange

 

 

 

R – SHLD

2.4 - 2.5 Volts DC

 

 

 

 

Damage typically occurs when the communications loop is exposed to excessive voltage, as may occur during installation, due to wiring errors. The driver chips are socketed on all boards to facilitate servicing. It is unusual for driver chips to fail during normal operation. Almost all failures occur due to wiring related problems.

Measurements

Minor variances may not indicate a problem if both tests indicate similar values.

Note:

4-30

Start-Up and Troubleshooting

Page 112
Image 112
Heat Controller Water Source Heat Pump TLocal– SHLDLoop, AcceptableRange, WattMaster WHP, Section, Diagram, Measurements