3.2Loop Controller Inputs & Outputs

WattMaster WHP

Section 4

 

 

3.2Loop Controller Inputs & Outputs

3.2.1Analog Inputs

AIN1 - Return Water Temp - This input accepts a two wire 10K Type III ther- mistor temperature sensor. The sensor measures 10,000 Ohms @ 77°F. The re- sistance drops as the temperature increases. The sensor is connected between this terminal and the GND terminal.

AIN2 - Supply Water Temp - This input accepts a two wire 10K Type III ther- mistor temperature sensor. The sensor measures 10,000 Ohms @ 77°F. The re- sistance drops as the temperature increases. The sensor is connected between this terminal and the GND terminal.

AIN3 – Proof of Flow/Loop Pressure - This input accepts a differential pressure contact closure for proof of flow or a 0-50 PSI (0-5VDC) pressure transducer sig- nal.

AIN4 - Outdoor Air Temp - The OA temperature is used to determine if pumps should be turned on during off periods, to prevent freezing. When the OA tem- perature is below 40° F, the pumps will be turned on.

AIN5 - Manual Reset Input - Used to restart equipment after alarm condition has occurred. When this input is shorted to GND by a momentary pushbutton, a signal to restart is sent.

AIN7 Phase Loss – If a phase monitor is being used, a normally open contact is connected here. When a loss of phase is detected, this contact closes shutting down the Loop Controller.

GND - Common return wire. This point is tied to ground on the Loop Controller.

3.2.2Analog Output

This connector carries a 0-10 volt control signal for the following items:

AOUT1- Pump VFD Signal - If you have selected the variable speed pump op- tion this output signal is used to control the loop pressure.

AOUT2 - Proportional Heat Signal - This output may be used when a modulat- ing signal is required to control heat addition temperature.

GND - Common return wire, this point is tied to GND on the Loop Controller.

4-10

Start-Up and Troubleshooting