Image 124
5.6Pressure Sensor Voltage Chart

WattMaster WHP

Section 4

 

 

5.6Pressure Sensor Voltage Chart

 

 

 

PRESUREPSI0

MILIAMPSCURRENT4.00

INPUVOLAGE1T.00VDC*AT

1

4.32

1.08

2

4.64

1.16

3

4.96

1.24

4

5.28

1.32

5

5.60

1.40

6

5.92

1.48

7

6.24

1.56

8

6.56

1.64

9

6.88

1.72

10

7.20

1.80

11

7.52

1.88

12

7.84

1.96

13

8.16

2.04

14

8.48

2.12

15

8.80

2.20

16

9.12

2.28

17

9.44

2.36

18

9.76

2.44

19

10.08

2.52

20

10.40

2.60

21

10.72

2.68

22

11.04

2.76

23

11.36

2.84

24

11.68

2.92

25

12.00

3.00

26

12.32

3.08

27

12.64

3.16

28

12.96

3.24

29

13.28

3.32

30

13.60

3.40

31

13.92

3.48

32

14.24

3.56

33

14.56

3.64

 

 

 

 

PRESUREPSI34

MILIAMPSCURRENT14.88

 

INPUVOLAGE3T.72VDC*AT

35

15.20

3.80

36

15.52

3.88

37

15.84

3.96

38

16.16

4.04

39

16.48

 

4.12

40

16.80

4.20

41

17.12

4.28

42

17.44

4.36

43

17.76

4.44

44

18.08

4.52

45

18.40

4.60

46

18.72

4.68

47

19.04

4.76

48

19.36

4.84

49

19.78

4.92

50

20.00

5.00

*Notes:

1.Use the voltage column to compare the meter voltage with the sensor connected to the controller and with the controller pow- ered.

2.Read voltage with meter set on DC volts. Place the “-”(minus) lead on GND terminal and the “+”(plus) lead on the sensor input terminal being investigated.

3.If the voltage is less than 0.05 VDC, then the sensor or wiring is “shorted” or “open”

4-42

Start-Up and Troubleshooting

Page 124
Image 124