Default76°F

Section 3

WattMaster WHP

 

 

Setpoint Screen #3

WPHEATINGADDITIONLoopSetpoints° SetpointtageDeadband......:xx°F

If the controlling water temperature drops below this Setpoint, the Heat Addition or Boilers begin to stage on. As the temperature continues to drop below the Setpoint by the Deadband amount, an additional stage is added. Each additional stage can only activate if the temperature drops below the Setpoint by the number of active stages times the deadband value.

Example: There are 2 stages on, a 3° deadband and the setpoint is 79°

79° - 2 x 3° = 73° before stage 3 can activate

 

 

 

Setpoint

Minimum50°F

 

Stage Deadband

1°F

 

Default76°F

3°F

Maximum99°F

10°F

Setpoint Screen #4

StageWPHEATINGADDITIONLoopDelaySetpoints...:xM

The Staging Delay period must also be satisfied before an additional boiler or heat addition stage can be activated.

The maximum number of heat addition stages are programmed on this screen also.

Stage Delay

Minimum1 Minute

1DefaultMinute

60MaximumMinutes

Setpoint Screen #5

°

OAWHPSetpointFREEZEPROTECTIONLoop.....Setpoints:xx Maximum99°F

If the outdoor air temperature drops below this setpoint, the pump will be energized to prevent the water lines from freezing.

FSetpoint

Minimum-50°F

Default40°F Maximum50°F

3-28

Progr mming

Page 76
Image 76
Heat Controller Water Source Heat Pump manual Default40F Maximum50F, Default76F, Minimum-50F, Maximum99F