Heat Controller Water Source Heat Pump manual WattMaster WHP, Section, Start-Upand Troubleshooting

Models: Water Source Heat Pump

1 126
Download 126 pages 9.48 Kb
Page 102
Image 102
WHP Controller Address Switch Setting

WattMaster WHP

Section 4

 

 

4.5.2Loop Controller Addressing

The Loop Controller address should always be set for address #30. A maximum of 29 WHP Controllers on the loop that contains the Loop Controller. All other loops may have 30 WHP Controllers. (Refer to Figure 2-10for more detail)

4.5.3WHP Controller Addressing

NOTE:

IGNORE ANY MARKINGS

OR NUMBERS ON THE SWITCH

USE THE CHART!

To determine the boards address, add the values of all the switches which are toggled down in the direction of the arrow

NOTE:

ADDRESS 30 CANNOT BE USED

ON THE LOOP THAT HAS THE WHP LOOP

CONTROLLER ATTACHED. ADDRESS 30

ON THAT LOOP IS RESERVED FOR THE

WHP LOOP CONTROLLER.

CAUTION:

YOU MUST POWER DOWN THE CONTROLLER

AFTER CHANGING THE ADDRESS SWITCHES

IN ORDER FOR ANY CHANGES TO TAKE EFFECT.

ALWAYS REMOVE THE COMMUNICATIONS LOOP

PRIOR TO DISCONNECTING POWER. RECONNECT

POWER AND THEN RECONNECT THE COMMUNICATIONS

LOOP TO THE CONTROLLER.

4Figure-204-10:

WHP Controller Address Switch Setting

Start-Up and Troubleshooting

Page 102
Image 102
Heat Controller Water Source Heat Pump manual WattMaster WHP, Section, Start-Upand Troubleshooting, Use The Chart