WattMaster WHP | Section 4 |
|
|
4.5.2Loop Controller Addressing
The Loop Controller address should always be set for address #30. A maximum of 29 WHP Controllers on the loop that contains the Loop Controller. All other loops may have 30 WHP Controllers. (Refer to Figure
4.5.3WHP Controller Addressing
NOTE:
IGNORE ANY MARKINGS
OR NUMBERS ON THE SWITCH
USE THE CHART!
To determine the boards address, add the values of all the switches which are toggled down in the direction of the arrow
NOTE:
ADDRESS 30 CANNOT BE USED
ON THE LOOP THAT HAS THE WHP LOOP
CONTROLLER ATTACHED. ADDRESS 30
ON THAT LOOP IS RESERVED FOR THE
WHP LOOP CONTROLLER.
CAUTION:
YOU MUST POWER DOWN THE CONTROLLER
AFTER CHANGING THE ADDRESS SWITCHES
IN ORDER FOR ANY CHANGES TO TAKE EFFECT.
ALWAYS REMOVE THE COMMUNICATIONS LOOP
PRIOR TO DISCONNECTING POWER. RECONNECT
POWER AND THEN RECONNECT THE COMMUNICATIONS
LOOP TO THE CONTROLLER.
WHP Controller Address Switch Setting | |