Section 3 | WattMaster WHP |
|
|
Status Screen #7
LoopNoControlAlarms!v1.06
Line 2 - | Pump Failure or Blank Line |
Line 3 - | Hi Control Water Temp |
| Lo Control Water Temp |
Line 4 - | Fire/Smoke Alarm |
| |
| Phase Shutdown |
Note: If no alarms exist, then the screen displays the message shown for No Alarms! If ANY alarm exists, then the three lines display one of the messages shown above.
The Fire/Smoke Alarm is generated as follows:
If the NC (normally closed) contact from a firestat or smoke detector that is wired between GND and AIN1, on the Analog Input expansion board, opens, the Fire/Smoke Alarm is generated.
The Phase Shutdown Alarm is generated as follows:
If the NO (normally open) contact from a phase monitoring device, that is wired between GND and AIN7 is made, the Phase Shutdown Alarm is generated.
Status Screen #8
| Line 2 - | Message Only |
| Line 3 - | Pump #1 Hours and Minutes Run Time |
#Loop1:2PumpxxxxxHrsxxMinControlRunTimesv1.06 | Line 4 - | Pump #2 Hours and Minutes Run Time |
Programming |