Status Screen #7

Section 3

WattMaster WHP

 

 

Status Screen #7

LoopNoControlAlarms!v1.06

Line 2 -

Pump Failure or Blank Line

Line 3 -

Hi Control Water Temp

 

Lo Control Water Temp

Line 4 -

Fire/Smoke Alarm

 

 

Phase Shutdown

Note: If no alarms exist, then the screen displays the message shown for No Alarms! If ANY alarm exists, then the three lines display one of the messages shown above.

The Fire/Smoke Alarm is generated as follows:

If the NC (normally closed) contact from a firestat or smoke detector that is wired between GND and AIN1, on the Analog Input expansion board, opens, the Fire/Smoke Alarm is generated.

The Phase Shutdown Alarm is generated as follows:

If the NO (normally open) contact from a phase monitoring device, that is wired between GND and AIN7 is made, the Phase Shutdown Alarm is generated.

Status Screen #8

 

Line 2 -

Message Only

 

Line 3 -

Pump #1 Hours and Minutes Run Time

#Loop1:2PumpxxxxxHrsxxMinControlRunTimesv1.06

Line 4 -

Pump #2 Hours and Minutes Run Time

3-26

Programming

Page 74