Heat Controller Water Source Heat Pump Default1, WHP#1Setpoints, Default3F, Minimum0F, Maximum5F

Models: Water Source Heat Pump

1 126
Download 126 pages 9.48 Kb
Page 62
Image 62
Minimum0°F

Section 3WattMaster WHP

Setpoint Screen #2

 

 

 

The Unoccupied Heating and Cooling Setbacks are programmed

UnccupiedoWHP#1Setpoints°

on this screen. The Cooling SetUp is added to the Occupied

Cooling Setpt to create the Unoccupied Cooling Setpoint. The

Heat

Set

.:xx°F

Heating SetBack is added to the Occupied Heating Setpt to

 

Bk

Col

 

up

 

create the Unoccupied Heating Setpt.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cool SetUp

Minimum1°F

 

Default10°F

Maximum30°F

 

 

Heat SetBack

-1°F

 

-10°F

-30°F

 

 

 

 

 

 

 

Setpoint Screen #3

WHP#1Setpoints° SOVurationx.lidePDadbandEffect:.xx°HrF

If the Space Temperature Sensor has the optional slide adjustment, then the Slide Effect is the maximum amount of change that it can have on the Heating and Cooling Setpoint and it is programmed here.

The SP Deadband is divided in half across the current heating and cooling setpoint, and is used in staging the heating and cooling on or off.

If you have an override pushbutton on the space sensor, the OV Duration is the length of time the unit will be in the occupied mode after pushing the button

 

 

 

 

Slide Effect

Minimum0°F

Default3°F

Maximum5°F

SP Deadband

0°F

1°F

20°F

OV Duration

0.0 Hr

1.0 Hr

8.0 Hr

 

 

 

 

Setpoint Screen #4

 

WHP#1Setpoints

 

If the Heat Pump is configured to operate with

 

Reversing

 

 

Valve, relay #5 can be configured as second stage for either

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cool

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

heating or cooling or both. If the Heat Pump is configured for

 

HeatingStages:x

 

 

 

 

individual heating and cooling, this determines how many of

 

 

 

each stage there are.

 

 

 

Maximum

 

 

 

Cooling Stages

Minimum0

Default1

 

2

 

 

 

Heating Stages

0

1

 

 

2

 

 

 

 

 

 

 

 

 

3-14

 

 

 

 

Progr

ing

Page 62
Image 62
Heat Controller Water Source Heat Pump manual Default1, WHP#1Setpoints, Default3F, Minimum0F, Maximum5F, Cool