TLocal–LoopG

WattMaster WHP

Section 4

 

 

5.3.3Checking the CommLink II Driver

Diagram

Overview

This test checks for proper Network loop voltages coming from the CommLink II.

The Loop LED (located on the front panel) should “flicker” when the CommLink II is

Tip:attempting to communicate. The Loop LED will flicker more noticeably for a few seconds when first powered up. If the LED does not flicker, the unit is not function- ing.

Proper loop voltages are essential for reliable communications. It is normal to see fluctua- tions at this point on the CommLink II. The average value should be close to the acceptable range described below. Values will vary upon initial powerup for about 10-15 seconds as the unit attempts to communicate.

Measurements

 

 

 

TLocalLoopG

2.4 - 2.5 Volts DC

AcceptableRange

(SHLD)

 

 

 

 

 

R – G

2.5 - 2.7 Volts DC

 

(SHLD)

 

 

 

 

 

Action

If voltages are tooConditionhigh or too low on either side

1.The CommLinkActionII has a damaged comm driver chip. Replace the driver chip. See instructions in section 1.3.11 for “Comm Driver Chip Replacement”.

2.The CommLink II is defective.

4-26

Start-Up and Troubleshooting

Page 108
Image 108