Section 2 | WattMaster WHP |
|
|
MiniLink Addressing
Connect To Next
MiniLink And/Or
CommLink On
Network Loop
Network Loop
19200 Baud
All Communication Loop Wiring Is Straight Through
MiniLink Communications Interface
ADD
1
T NETWORK 42
SH | 8 |
16 | |
R | 32 |
|
OFF >
24VACLine Voltage
T | T | T | T |
|
SH | SH | SH | SH | 24VAC |
R | R | R | R | GND |
|
|
| T |
|
Local Loop |
| SH |
| |
| R |
| ||
|
| |||
9600 Baud |
|
|
| |
| Connect To Next |
| ||
| Controller or |
| ||
| System Manager |
| ||
|
|
|
| ADD |
| Caution! |
|
| 1 |
|
|
| 2 | |
| The MiniLinks Must Have Address Switches Set Between 1 | |||
| 4 | |||
| And 30 (Up To 30 MiniLinks Are Allowed Per WHP System | |||
| 8 | |||
| System). The MiniLinks Should Be Addressed In | |||
| Consecutive Order Starting With Address #1. AddressLOOP#1 | 16 | ||
| Must Be Present On The Loop For The System To Function. | 32 |
Note:
The Power To The MiniLink Must Be Removed And
Reconnected After Changing The Address Switch
Settings In Order For Any Changes To Take Effect.
Required VA For Transformer
MiniLink = 6VA Min.
See Note 1.
These Switches Must Be
In The OFF Position
As Shown
Caution:
Disconnect All Communication Loop Wiring From The MiniLink Before Removing Power From The MiniLink. Reconnect Power And Then Reconnect Communication Loop Wiring.
Notes: | 1.)24 VAC Must Be Connected So |
| That All Ground Wires Remain |
| Common. |
| 2.)All Wiring To Be In Accordance |
| With Local And National Electrical |
| Codes And Specifications. |
| 3.) All Communication Wiring To Be |
| 2 Conductor Twisted Pair With |
| Shield. Use Belden #82760 Or |
| Equivalent. |
| MiniLink |
| Address Switch |
Address Switch Shown Is | Address Switch Shown Is |
Set For Address 1 | Set For Address 4 |
The Address For Each MiniLink
Must Be Unique To The Other MiniLinks
On The Network Loop. Loop #1 MiniLink
Should Be Addressed As #1
Loop #2 MiniLink Should Be Addressed
As #2 Etc..
MiniLink Address Switch Setting
Figure2-13:
| Installation and Wiring |