Heat Controller Water Source Heat Pump 4Figure-2, WattMaster WHP, Section, System Wiring Overview

Models: Water Source Heat Pump

1 126
Download 126 pages 9.48 Kb
Page 84
Image 84
WattMaster WHP

WattMaster WHP

Section 4

 

 

COMPUTER

 

(OPTIONAL)

 

RS-485

Comm Loop

 

 

Room Sensor

 

 

with Optional

 

 

Override & Adj.

110/24 VAC

 

 

Power Pak

 

Supply

 

 

Modem

 

Air

110/24 VAC

Sensor

(Optional)

Power Pak

 

 

 

CPU

24 VAC

Dirty Filter Alarm

or Leaving Water Temp

F

Typical WHP Controller Wiring

MR

TR

 

 

 

 

SD

 

 

 

 

 

 

 

 

RD

 

 

 

 

OH

CD

 

 

 

 

 

AA

 

 

 

 

HS

C

 

 

Network Loop

 

 

 

OMM LI

 

 

RS-485

NK II

 

 

P

M

O

19200 Baud

L

 

 

 

O

C

 

 

O O

M

 

 

P

ED

 

 

 

M

 

CommLink II

WAT

TMASTER

 

 

 

 

Multiple Loop

 

 

CON

NC

 

 

 

 

 

 

TRO

 

 

 

 

 

 

LS,I

 

 

Interface

 

 

 

 

Local Loop

 

 

 

 

 

 

 

 

 

MiniLink

RS-485

 

 

 

Loop # 1

9600 Baud

 

 

 

 

 

 

System Manager

 

 

 

 

24VAC

 

 

 

 

MiniLink

03/31/04

ALARMS

 

 

 

 

 

 

WED

 

 

 

 

 

 

03:38PM

 

 

 

 

 

OCCUPIED

 

 

Loop # 2

NO

 

 

 

 

 

 

 

 

 

24VAC

Local Loop

24VAC

 

 

 

 

 

 

 

 

 

 

 

RS-485

 

 

 

 

 

 

9600 Baud

 

 

 

 

 

Typical Network & Local Loop Wiring

 

 

 

 

2 Conductor Twisted Pair with Shield

 

 

 

 

(Beldon #82760 or Equivalent)

 

 

MiniLink

 

 

 

 

Loop # 3

 

 

 

 

 

 

 

Local Loop

 

 

 

 

24VAC

RS-485

 

 

 

 

 

9600 Baud

#1

CPU

#1

CPU

#1

CPU

Loop #1

#30

 

WHP

CPU

Controllers

 

Loop #2

#30

 

WHP

CPU

Controllers

 

Loop #3

#30

 

WHP

CPU

Controllers

 

NOTE: * Only One Outside Air Sensor is Required per WHP System

MiniLink

 

Loop # 4

*OutsideAir

 

 

Sensor

Loop # 4

24VAC

 

Notes:

WHP Loop

Controller

#1

CPU

See Note #3

Loop #4

WHP

Controllers

Local Loop

RS-485

9600 Baud

#29

CPU

1.) 24 VAC Must Be Connected

So That All Ground Wires

Remain Common.

2.) All Wiring To Be In Accordance

With Local And National Electrical

Codes and Specifications.

3.) The Local Loop With The Loop Controller Installed Can Only Have Up To 29

WHP Controllers Attached As The WHP Loop Controller Occupies Address #30.

4.) Systems may consist of up to 20 Local Loops (600 WHP Controllers). Consult

factory for systems that exceed these quantities.

4Figure-2

4-1:

System Wiring Overview

Start-Up and Troubleshooting

Page 84
Image 84
Heat Controller Water Source Heat Pump 4Figure-2, WattMaster WHP, Section, Start-Upand Troubleshooting, Modem, MiniLink