WattMaster WHP | Section 3 |
|
|
Setpoint Screen #17
WHPHeat#1StageSetpoints#2°
SATLockout:60F
This setpoint is to shut the heating off when the supply air temperature is too warm. When the supply air temperature is above this setpoint, it will prevent the second stage of heat from coming on.
|
|
|
|
Max Effect | Minimum30°F | Default60°F | Maximum200°F |
Setpoint Screen #18
| SENSORCALIBRATION° | °° | ||
WPC |
| xxxx.x |
| |
S |
| °° | °° | |
| ATxxx.x°° | .x°° |
The Thermister Type III Sensor readings can be calibrated. Enter Positive values to increase the reading or Negative values to decrease the reading. If no sensor is attached, the calibration offset will still allow a value to be input and read for diagnostic purposes.
|
|
|
|
|
Space Sensor | SPC | Default0.0°F | Maximum+100.0°F | |
Supply Air Sensor | SAT | 0.0°F | +100.0°F | |
Water Sensor | WAT | 0.0°F | +100.0°F |
Setpoint Screen #19
| Select if you want the notification LED on the front of the |
| System manager to illuminate when an alarm occurs. If |
| Enabled is selected, any WHP alarm will cause the Alarm |
| LED on the front panel to light up. If Disable is selected, the |
| Alarm LED will not light up but the alarm will still show up in |
UseAlarms:WHPLeft/Right#1SetpointsEnabledArrow | the Status screen. |
Note: You must do a Rebuild Alarm Map after all controllers are powered up and communicating.
Programming |