Heat Controller Water Source Heat Pump manual WHP Sequence of Operation, HVAC Mode of Operation

Models: Water Source Heat Pump

1 126
Download 126 pages 9.48 Kb
Page 12
Image 12
WHP Sequence of

Section 1

WattMaster WHP

 

 

WHP Sequence of

Operation

HVAC Mode of Operation

There are four possible modes of operation. These are Cooling Mode, Heating Mode, Vent Mode, and the Off Mode. The HVAC mode of operation is calculated the same way in both occupied and unoccupied modes of operation.

Off Mode The schedule is off and no overrides are active. There is no heating or cooling demand in the space. Under these conditions, all outputs will be off and the analog output will be set to 0.0 vdc.

Vent Mode No heating or cooling demand exists during the occupied mode of operation. The fan will be on if the WHP is programmed for Constant Fan operation. The compressor demand request will not be sent to the Loop Controller. If no WHP units are sending a request, the Loop Controller will discontinue operation after 15 minutes.

Cool Mode A cooling demand is generated when the space temperature rises half the amount of the Deadband Setpoint above the currently active Cooling Setpoint. The space is considered satisfied when it drops that amount below the Cooling Setpoint.

Heat Mode A heating demand is generated when the space temperature drops half the amount of the Deadband Setpoint below the currently active Heating Setpoint. The space is considered satisfied when it rises that amount above the Heating Setpoint.

1-6

Design Guide

Page 12
Image 12
Heat Controller Water Source Heat Pump manual WHP Sequence of Operation, HVAC Mode of Operation