
WattMaster WHP | Section 3 |
|
|
Setpoint Screen #12
If you configured the system for Variable Speed Pumping with a Pressure Sensor for proof of flow, the Loop Controller can send a signal to all the Heat Pumps to open their Isolation Valves whenever a Hi Limit Pressure is exceeded. If the Heat Pumps do not control an Isolation Valve, then the only reaction is to
IsolatiWHPOpenifHiLimtLoponValvesPSI...Setpoints:isxxxPSIAboveSet reduce the variable speed pump voltage signal.
Hi Limit
Minimum1 PSI
Default50 PSI
Maximum50 PSI
Setpoint Screens #13
| ° |
| °° |
WT | °° |
| °° |
| xxx.x°° | .x°° | |
| |||
RSENSORCALIBRATION.x | |||
S |
| xxxx |
|
OA |
|
|
The Thermister Type III Sensor readings can be calibrated. Enter a Positive value to increase the reading or a Negative value to decrease the reading. If no sensor is attached, the calibration offset will still allow a value to be input and read for diagnostic purposes.
|
|
|
|
|
Return Water | RWT | Default0.0°F | Maximum+10.0°F | |
Supply Water | SWT | 0.0°F | +10.0°F | |
Outdoor Air | OAT | 0.0°F | +10.0°F |
Note: Due to memory limitations in the Loop Controller, the maximum amount of calibration offset is 10.0°F.
Setpoint Screen #14
WHPAlarms:EnabledLoopSetpoints
Alarms can be configured to light the LED on the front of the System Manager by setting Alarms to Enabled, if you do not wish to report alarms, select Disabled.
Setpoint Sc een #15
UseLeft/RightArrow
UseRWHPly1:ADDITIONelayLeft/RoopConfurationsSetpointsightArrow
Use this screen to configure the relays on the expansion board for heat ADDITION, REJECTION or NOT USED. All 8 relays come up one at a time.
Programming |