Heat Controller Water Source Heat Pump Pump VFD Control, Compressor Control, WattMaster WHP, 1-11

Models: Water Source Heat Pump

1 126
Download 126 pages 9.48 Kb
Page 17
Image 17
Pump VFD Control

WattMaster WHP

Section 1

 

 

pump exceeds the first pumps run time by the same amount. This keeps both pumps with roughly the same number of hours on each pump. Changeover occurs at the time the run time setpoint is exceeded. The running pump is shut off at the same time the standby pump is energized, this prevents any down time or alarms. The unit can be configured to control either the Loop Inlet temperature or the loop outlet temperature.

A user adjustable low outdoor air temperature setting of XX degrees will allow the unit to run the pumps continuously for protection against freezing.

If the pump is constant volume, and the pump has been started, it has 3 seconds to generate flow or the standby pump is activated. If the pump is controlled by a VFD, once it starts, it has 60 seconds to generate flow and if it doesn’t the standby pump is activated. If the standby pump fails, an alarm is generated and the Loop controller deactivates any active heat rejection or addition stages. At the same time an alarm is generated, we energize relay #5 on the Loop Controller board so that it may used to turn on a local alarm signal.

Loop flow can be determined by a binary contact closure on input #3 or a 0 to 50 PSI pressure sensor on input #3. If a pressure sensor is used, the user can program the pressure setpoint that needs to be met for proof of flow.

Pump VFD Control

An optional Pump VFD signal can be modulated if the system is configured for proportional control and a pressure sensor is attached to analog input #3.

At a user defined rate, the VFD signal is ramped up when the pressure is below

a user defined setpoint by a user defined deadband. The signal ramps down when the pressure exceeds the setpoint by the deadband value. If the pressure ever exceeds the high pressure setpoint, an emergency override activates and begins cutting the VFD signal in half each time the control loop is polled by the software. This protects against run away over-pressurization.

The pump relay outputs are still activated and Lead/Lagged as described above and the pump relay remains on until the Request signal is removed, provided it has been operating for at least 15 minutes.

Compressor Control

Anytime a pump is running and proof of flow has been established, the compressor output is activated.

Design Guide

1-11

Page 17
Image 17
Heat Controller Water Source Heat Pump Pump VFD Control, Compressor Control, WattMaster WHP, Section, Design Guide, 1-11