Section 3

 

 

Setpoint Screen #5

MinWHPRunOffCycle#1Time:...StpointsxxMin

The Min Run Time determines how long the compressor must remain on once it has been activated. The Min Off Time determines how long the compressor must remain off once it is de-activated. The Min Cycle time determines how many times per hour the compressor can be started. If you entered 10 minutes, the compressor could start a maximum of 6 times in a one hour period.

 

 

 

 

Min Run Time

Minimum0

Default1 Min

Maximum20 Min

Min Off Time

0

6 Min

20 Min

Min Cycle

0

12 Min

60 Min

Setpoint Screen #6

 

 

 

 

 

 

To prevent rapid cycling between heating and cooling modes,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WHP#1Stpoints

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Changeover Delay

Minimum1

Default30 Min

Maximum60 Min

 

 

 

 

 

 

 

 

BetweenHat/CoolChangeover

you can enter a time period that must be satisfied before the

Setpoint ScreenDelay

changeover can occur.

 

 

 

#7

 

 

 

 

Modes......:xxMin.

 

Normally you would want to have an Enable Signal that gave

 

 

 

WHP#1

Sepoints

 

to run.

 

 

 

 

 

 

 

 

 

 

SignalSelect

 

 

assurance of water flow before you activate the heat pumps

 

 

compressor. If you need to operate without this enable signal,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

REQUIRED

 

 

 

 

 

 

EnableUseft/RighENABLE

tArrow

use the arrow keys to select the NO ENABLE REQUIRED

 

 

 

 

 

 

message. Otherwise, select the LOOP FLOW REQUIRED

message so that the signal must be present for the compressor