Heat Controller Water Source Heat Pump 5.5Temperature Sensor Resistance Chart, WattMaster WHP

Models: Water Source Heat Pump

1 126
Download 126 pages 9.48 Kb
Page 123
Image 123
5.5Temperature Sensor Resistance Chart

WattMaster WHP

Section 4

 

 

5.5Temperature Sensor Resistance Chart

TEMPERATUREº

RESISTANCE

VOLTAGEAT

-10F

93333Ω*

INPUT*4.620

-5

80531

4.550

0

69822

4.474

5

60552

4.390

10

52500

4.297

15

45902

4.200

20

40147

4.095

25

35165

3.982

30

30805

3.862

35

27140

3.737

40

23874

3.605

45

21094

3.470

50

18655

3.330

52

17799

3.275

54

16956

3.217

56

16164

3.160

58

15385

3.100

60

14681

3.042

62

14014

2.985

64

13382

2.927

66

12758

2.867

68

12191

2.810

69

11906

2.780

70

11652

2.752

71

11379

2.722

72

11136

2.695

73

10878

2.665

74

10625

2.635

75

10398

2.607

76

10158

2.577

78

9711

2.520

80

9302

2.465

TEMPERATUREº

RESISTANCE

VOLTAGEAT

82F

8893Ω*

INPUT*2.407

84

8514

2.352

86

8153

2.297

88

7805

2.242

90

7472

2.187

95

6716

2.055

100

6047

1.927

105

5453

1.805

110

4923

1.687

115

4449

1.575

120

4030

1.469

125

3656

1.369

130

3317

1.274

135

3015

1.185

140

2743

1.101

145

2502

1.024

150

2288

0.952

*Notes:

1.Use the resistance column to check the thermistor sensor while disconnected from the controllers (not powered).

2.Use the voltage column to check sensors while connected to powered controllers. Read voltage with meter set on DC volts. Place the “-”(minus) lead on GND terminal and the “+”(plus) lead on the sensor input terminal being investigated.

If the voltage is above 5.08 VDC, then the sensor or wiring is “open.” If the voltage is less than 0.05 VDC, the sensor or wiring is shorted.