5.4.1(continued)

WattMaster WHP

Section 4

 

 

5.4.1(continued)

AIN4

1.9 volts (100°F) - 3.6 volts (40°F)

Outdoor Air Temp

Typical is 2.5 volts @ 77°F

 

 

 

 

 

 

AIN5

If the input is OPEN, the voltage will be greater than 5.0 volts

Manual Reset

If the input is CLOSED, the voltage will be less than 0.5 volts

 

 

 

 

 

 

AIN7

If the input is OPEN, the voltage will be greater than 5.0 volts

Phase Loss

If the input is CLOSED, the voltage will be less than 0.5 volts

 

 

 

AIN1-Exp. Bd.

If the input is OPEN, the voltage will be greater than 5.0 volts

Fire Alarm

If the input is CLOSED, the voltage will be less than 0.5 volts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Caution: AIN1 – Fire/Smoke input must be connected

 

 

 

 

to the AIN1- GND terminal. If it is not used, a jumper must be

 

 

 

 

installed, since this is a normally closed contact input. If this

 

 

 

 

is not done the system will not operate.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIN2-Exp. Bd.

If the input is OPEN, the voltage will be greater than 5.0 volts

Request to Run

If the input is CLOSED, the voltage will be less than 0.5 volts

 

 

 

 

 

SWT, RWT, OATConditionInput voltage reads too

1. Check for shortsActionor other wiring errors.

low

 

2.

Defective Sensor. Check using the chart.

 

 

 

 

 

 

3.

High temperature at sensor. See chart.

 

 

SWT, RWT, OAT input voltage reads too

1. Check for open circuit wiring errors.

high

 

2.

Defective sensor. Check using the chart.

 

 

 

 

 

 

3.

Low temperature at sensor. See chart.

 

 

LPR (when optional 0-5VDC Loop Pres-

1. Check for shorts or other wiring errors.

sure Sensor is used) input voltage reads too

2.

Defective Sensor. Check using the chart.

low.

 

 

3.

High pressure at sensor. See chart.

 

 

 

 

 

LPR (When Loop Pressure Switch is used)

1. Check for open circuit wiring errors.

input voltage reads too high.

 

 

 

 

 

 

 

 

 

 

 

4-36

Start-Up and Troubleshooting

Page 118
Image 118
Heat Controller Water Source Heat Pump manual 5.4.1continued, is not done the system will not operate