Menu Setpoints

WattMaster WHP

Section 3

 

 

Menu Setpoints

Full Setpoint Access

If you selected the Menu key from the first menu screen you can access all setpoints available from any unit on your system. You must be a Level 2 user to access these setpoints. If you haven’t already been asked to enter the passcode, you will be asked before the Full Setpoint Access menu is displayed. This prevents the casual user from being able to affect the operation

4Rbuild3NwPasscodes21)StAccessTimeUnitsAlarm&DateMap of your heat pump system.

Set Time & Date

The System Manager has its own built in Real Time Clock. It broadcasts this time once a day, at midnight, to synchronize all of the WHPs on your system. Although the times are displayed on the Main Screen in a standard 12-hour format, they are programmed using the 24-hour Military format. Once the time has been entered, it is also broadcast immediately to all other units on the system. That means that you only need to program the System Manager time to set the Real Time Clocks for all units on your system. In order for the System Manager to broadcast the time and date to all controllers, they must be powered up and communicating.

Programming Time

 

Day

-

Enter the Day of the Week (0 to 6) with

 

 

 

Sunday = 0

 

Hours (Hr)

-

Enter Hours in 24-Hour Military Format

 

 

 

 

(1700 = 5:00 PM)

EnterDayProgramMinutesHr(Sunday=0.(0Time/Date-23):5391 Minutes

-

Enter the Minutes (0 to 59)

Programming

3-9