○Fire and fault routing signalling should be tested.
WARNING: Before testing, the engineer must be aware both of the operation of all devices fitted to the auxiliary circuits and of the consequences of their operation.
13.4Pre-Commissioning Wiring Check
NOTE: This
1.Ensure that no devices are connected to the detection zones and alarm circuits, but that the cables are linked through at the device locations to achieve a continuous circuit.
2.Ensure that the resistance of all cables to earth and between cores is at least 2MΩ. Check the following:
i)Positive to earth resistance is 2MΩ or greater.
ii)Negative to earth resistance is 2MΩ or greater.
iii)Positive to negative resistance is 2MΩ or greater.
3.Connect a wire link as the
Correct polarity throughout all circuits must be maintained. Rectify any faults.
All bells, detector heads and call points should now be connected and the correct
Warning: Intrinsically safe zone arrangement.
○
○In order for detector head removal monitoring to function correctly when resistors are used as the
○The panel must be configured to monitor Intrinsically Safe zones.
○The first device on an Intrinsically Safe zone must be an I.S. Zener Barrier or Galvanic Isolator. Detectors and Manual Call Points on the Safe side of the barrier are not permitted.
○To comply with the requirements of BS5839, all manual call points should be located in the zone cabling between the I.S. Barrier/Isolator and the first detector. Any manual call point or detector located on the
Page 20 of 40