13.5Powering up
1.Prior to powering up, the panel will have been installed in accordance with the installation instructions, all cabling will have been fully installed and tested, glanded into the panel enclosure but not connected to the panel terminals. The mains supply should be isolated externally to the panel.
2.Check the battery connections are correct.
3.Remove the mains supply fuse from the panel mains terminal block. Once the permit to energise the mains supply is in place, energise the mains and check the voltage and polarity are correct before replacing the panel fuse.
4.The panel will power up and if all the end of line devices are correctly terminated in the panel and the battery is OK, the panel should be silent, displaying only the Power Supply On indication.
5.Turn the Access keyswitch to “1” and press the Test Display button. The panel should respond by lighting all indications and sounding the buzzer. This will continue for a few seconds after the button is released.
13.6Configuration.
13.6.1Basic Default Configuration
When first powered up, the
The basic default mode is:
○All zones latching fire,
○Fire Routing, Fire Protection and Sounder outputs not delayed.
13.6.2Site-Specific Configuration.
It is possible to tailor the functionality of the
13.7Commissioning Procedure
After completion of the
13.7.1Alarm Circuits
1.Remove the resistor from the first alarm circuit terminal and connect the first alarm circuit wiring to the terminals, observing correct polarity. Check that any alarm fault indications clear after a few seconds.
2.Use the Alarm Test facility [see
3.Deselect the Alarms Test condition or if “Evacuate” was used, press silence alarms to stop the sounders operating.
4.Repeat steps 1 to 3 for the second and any subsequent alarm circuits.
Page 21 of 40