![](/images/new-backgrounds/1052400/5240071x1.webp)
16.2Configuring the Clock Module
The Clock Module is configured by setting Link 1 and DIL switch 1. These are both located on the rear of the C1651 Clock Module PCB [accessed by opening the panel door].
Link 1
Position Selected |
| Function |
| |
|
|
|
|
|
Fitted |
|
| 1st Fire Alarm Time Mode selected | |
Removed |
|
| Day/Night Mode selected | |
|
|
|
|
|
|
|
|
| |
Link 1 | DIL Switch 1 |
| ||
|
|
|
| |
| Pole | Position Selected | Function | |
|
|
|
| |
Removed | 1 | Left [Off] | Clock Module Menu configuration disabled | |
|
|
|
| |
| 1 | Right [On] | Clock Module Menu configuration enabled | |
|
|
|
| |
Fitted | 1 | Left [Off] | No effect | |
|
|
|
| |
| 1 | Right [On] | No effect | |
|
|
|
| |
Removed | 2 | Left [Off] | Day/Night mode and Fire Event Counter mode | |
|
|
|
| enabled. |
|
|
|
| |
Removed | 2 | Right [On] | Day/Night mode and Fire Event Counter mode | |
|
|
|
| disabled. |
|
|
|
| [To zero the Fire Event Counter, select “On” |
|
|
|
| momentarily then return to “Off”]. |
|
|
|
| |
Fitted | 2 | Left [Off] | 1st Alarm Fire Time and Fire Event Counter | |
|
|
|
| Mode enabled |
Fitted | 2 | Right [On] | 1st Alarm Fire Time and Fire Event Counter | |
|
|
|
| Mode disabled. |
|
|
|
| [To zero the Fire Event Counter, select “On” |
|
|
|
| momentarily then return to “Off”]. |
Table 4 – C1651 Clock Module DIL switch 1 and Link 1 Settings