APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont)
SCREEN NAME | PASSWORD |
| POINT NAME | EDITABLE | RANGE | DEFAULT | NOTES | |
LEVEL |
| |||||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| Auto= Intermittant operation during both |
|
|
|
|
|
|
|
| occupied and unoccupied periods/ |
|
|
|
|
|
| Auto/Continuous/ |
| Continuous = Intermittant during unoccupied |
|
|
|
| Fan Mode | X | Continuous | periods and continuous during occupied | |
|
|
|
| Always On | ||||
|
|
|
|
|
|
| periods/Always on = fan operates | |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| continuously during both occupied and |
|
|
|
|
|
|
|
| unoccupied periods |
|
|
|
| Fan On Delay | X | 0 - 30 sec | 10 sec | Defines the delay time before the fan begins |
|
|
|
| to operate after heating or cooling is started | ||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| Defines the amount of time the fan will |
|
|
|
| Fan Off Delay | X | 0 - 180 sec | 45 sec | continue to operate after heating or |
|
|
|
|
|
|
|
| cooling is stopped |
|
|
|
| Heating Enable | X | Disable/Enable | Enable | Provides capability to manually |
|
|
|
| disable heating operation | ||||
|
|
|
|
|
|
|
| |
|
|
|
| Cooling Enable | X | Disable/Enable | Enable | Provides capability to manually |
|
|
|
| disable cooling operation | ||||
|
|
|
|
|
|
|
| |
|
|
|
| Minimum SAT in | X | 40 - 60 ° F | 50 ° F | Defines the minimum acceptable operating |
|
|
|
| Cooling | temperature for the Supply Air | |||
Configuration |
|
|
|
|
| |||
|
| Maximum SAT in | X | 80 - 140 ° F | 110 ° F | Defines the maximum acceptable operating | ||
|
|
|
| |||||
|
|
|
| Heating | temperature for the Supply Air | |||
| → | Admin Password |
|
|
|
| ||
|
|
|
|
|
| Normally set to 100% if 2 position damper | ||
|
| level access only |
| Damper Ventilation |
|
|
| |
|
|
| X | 0 - 100% | 100% | type or set to minimum ventilation position if | ||
| Unit |
|
| Position | ||||
|
|
|
|
|
| damper type = DCV | ||
Configuration |
|
|
|
|
|
| ||
|
| DCV Maximum Vent | X | 0 - 100% | 100% | Usually set at 100% - Used to limit maximum | ||
|
|
|
| |||||
|
|
|
| Position | damper opening in DCV mode | |||
|
|
|
|
|
|
| ||
|
|
|
| Filter Alarm Timer | X | 0 - 9999 hrs | 0 hrs | Disables Filter Alarm if set to 0 |
|
|
|
| Pushbutton Override | X | Disable/Enable | Enable | Enables Override Feature on Rnet sensor |
|
|
|
| SPT Sensor Set Point | X | Disable/Enable | Enable | Enables Set Point adjustment capability |
|
|
|
| Adjustment | on Rnet Sensor | |||
|
|
|
|
|
|
| ||
|
|
|
| Lockout Cooling if |
| Cooling is locked out when OAT is less than | ||
|
|
|
| X | configured value and OAT is actively being | |||
|
|
|
| OAT < | ||||
|
|
|
|
|
|
| broadcast | |
|
|
|
|
|
|
|
| |
|
|
|
| Lockout Heating if |
| 35 - 150 ° F | 150 ° F | Heating is locked out when OAT is greater |
|
|
|
| X | than configured value and OAT is actively | |||
|
|
|
| OAT > | ||||
|
|
|
|
|
|
| being broadcast | |
|
|
|
|
|
|
|
| |
|
|
|
| Power Fail Restart | X | 0 - 600 sec | 60 sec | Delay before equipment starts |
|
|
|
| Delay | ||||
|
|
|
|
|
|
|
| |
|
|
|
| Occupancy Schedules | X | Disable/Enable | Enable | Enables unit occupied |
|
|
|
| Set Point Separation | X | 2 - 9 ° F | 4 ° F | Used to enforce minimum |
|
|
|
| set point separation | ||||
|
|
|
|
|
|
|
| |
|
|
|
| Test Mode | X | Disable/Enable | Disable | Used to enable test mode. Will automatically |
|
|
|
| reset to disable after 1 hour | ||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| Used to test all fan speeds. Sequences fan |
|
|
|
| Fan Test | X | Disable/Enable | Disable | from low to high and operates each speed for |
|
|
|
|
|
|
|
| 1 minute. Resets to disable on completion |
|
|
|
| Fan Speed |
| Off/Low Speed/Medium |
| Displays current fan operation |
|
|
|
|
| Speed/High Speed/On |
| ||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| Used to test compressor cooling and heating |
|
|
|
|
|
|
|
| operation. Sequences cooling stage 1, then |
|
|
|
| Compressor Test | X | Disable/Enable | Disable | stage 2, then heating stage 2 and reduces |
|
|
|
|
|
|
|
| capacity to stage 1. Operates for 1 minute per |
|
|
|
|
|
|
|
| step. Resets to disable on completion. |
Configuration |
|
|
|
|
|
| Used to test dehumification mode - | |
| → |
|
| Dehumidification Test | X | Disable/Enable | Disable | Operates for 2 minutes. Resets to |
|
|
|
|
|
|
| disable on completion. | |
|
|
|
|
|
|
|
| |
|
| Admin Password |
|
|
| Inactive/Heating/Cooling/ |
|
|
| Service |
| Testing Compressor |
| Dehumidify/TimeGard |
| Displays compressor test mode | |
| level access only |
|
|
| ||||
|
|
|
|
| Wait |
|
| |
|
|
|
|
|
|
|
| |
| → |
|
|
|
|
|
| Used to test auxiliary heat. |
|
|
|
| Aux Heating Test | X | Disable/Enable | Disable | Sequences fan on and enables |
| Test |
|
| heating coil for 1 minute. Resets to | ||||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| disable on completion | |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| Used to test entering/return air water loop |
|
|
|
| H2O Economizer Test | X | Disable/Enable | Disable | economizer coil operation. Sequences fan on |
|
|
|
| and opens economizer coil water valve for 1 | ||||
|
|
|
|
|
|
|
| minute. Resets to disable on completion |
|
|
|
| Preposition OA | X | Disable/Enable | Disable | Used to preposition OA damper |
|
|
|
| Damper | actuator to set proper preload | |||
|
|
|
|
|
|
| ||
|
|
|
| Open Vent | X | Disable/Enable | Disable | Used to test OA damper operation |
|
|
|
| Damper 100% | ||||
|
|
|
|
|
|
|
| |
|
|
|
| SAT |
| ° F |
| Displays SAT |
|
|
|
| LCWT |
| ° F |
| Displays Leaving Condenser |
|
|
|
|
|
| Water Temperature | ||
|
|
|
|
|
|
|
| |
| LEGEND |
|
|
|
|
| ||
BAS — Building Automation System |
|
|
|
| ||||
DCV — Demand Controlled Ventilation |
|
|
|
| ||||
ECM | — Electronically Commutated Motor |
|
|
|
| |||
IAQ | — Indoor Air Quality |
|
|
|
|
| ||
OAT | — Outdoor Air Temperature |
|
|
|
|
| ||
RH | — Relative Humidity |
|
|
|
|
| ||
SAT — Supply Air Temperature |
|
|
|
|
| |||
SPT | — Space Temperature |
|
|
|
|
| ||
TPI | — Third Party Integration |
|
|
|
|
|