BC

Blower Contactor

CB

Circuit Breaker

Complete C

a50-8553

LEGEND

 

Field Line Voltage Wiring

Ground

 

Field Low Voltage Wiring

CO

Sensor, Condensate Overflow

Printed Circuit Trace

Solenoid Coil

ECR

Enthalpy Control Relay

FP1

Sensor, Water Coil Freeze Protection

FP2

Sensor, Air Coil Freeze Protection

GFI

Ground Fault Interrupter

HP

High-Pressure Switch

JW3

Clippable Field Selection Jumper

LAR

Low Ambient Relay

LOC

Loss of Charge Pressure Switch

MAS

Mixed Air Sensor

OAT

Outdoor Air Thermostat

PDB

Power Distribution Block

RVS

Reversing Valve Solenoid

TB

Terminal Block

TRANS — Transformer

Factory Line Voltage Wiring

Factory Low Voltage Wiring

Optional Wiring

Relay/Contactor Coil

Thermistor

Condensate Pan

Circuit Breaker

Relay Contacts - N.O.

Relay Contacts - N.C.

Temperature Switch

Switch - Low Pressure

Switch - High Pressure

Wire Nut

NOTES:

1.Compressor and blower motor thermally protected internally.

2.All wiring to the unit must comply with NEC (National Electrical Code) and local codes.

3.208/230-v transformers will be connected for 208-v operation. For 230-v operation, disconnect RED lead at L1, and attach ORG lead to L1. Close open end of RED lead.

4.FPI thermistor provides freeze protection for WATER. When using ANTIFREEZE solutions, cut JW3 jumper.

5.Typical heat pump thermostat wiring shown. Refer to thermostat installation instructions for wiring to the unit. Thermostat wiring must be “Class 1” and voltage rating equal to or greater than unit supply voltage.

6.Factory cut JW1 jumper and dry contact will be available between AL1 and AL2.

7.Transformer secondary ground via Complete C board standoffs and screws to control box. (Ground available from top two stand- offs as shown.)

Fig. 6 — 50RTP03-06 Units — Typical Control Wiring with Complete C Control

24

Page 24
Image 24