Carrier 50RTP03-20 specifications 50RTP08 Blower Performance Data cont

Models: 50RTP03-20

1 60
Download 60 pages 32.92 Kb
Page 16
Image 16

Table 8 — 50RTP08 Blower Performance Data (cont)

AIRFLOW

ESP

 

 

 

 

 

AIRFLOW (cfm) AT EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

(cfm)

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

1.1

1.2

1.3

1.4

1.5

1.6

1.7

1.8

1.9

2.0

 

 

bhp

1.29

1.37

1.44

1.52

1.59

1.67

1.74

1.82

1.89

2.00

2.04

2.12

2.20

2.28

2.36

2.44

2.52

2.60

2.67

2.77

2.84

3800

Sheave/Motor

A

A

A

A

A

A

C

C

C

E

E

E

E

E

E

E

E

E

E

E

E

rpm

712

740

764

792

816

840

864

888

908

932

952

976

1000

1020

1040

1060

1080

1100

1116

1136

1152

 

 

Turns Open

4.0

3.5

3.0

2.5

2.0

1.5

6.0

5.5

5.0

4.5

4.5

4.0

3.5

3.0

3.0

2.5

2.5

2.0

2.0

1.5

1.0

 

bhp

1.41

1.48

1.54

1.61

1.70

1.78

1.84

1.93

2.01

2.08

2.17

2.26

2.33

2.41

2.49

2.57

2.65

2.74

2.81

2.89

3900

Sheave/Motor

A

A

A

A

A

A

C

C

E

E

E

E

E

E

E

E

E

E

E

E

rpm

728

752

776

804

828

852

872

896

920

940

964

988

1008

1028

1048

1068

1088

1108

1124

1144

 

 

Turns Open

4.0

3.0

2.5

2.0

1.5

1.0

5.5

5.5

5.0

4.5

4.0

4.0

3.5

3.0

3.0

2.5

2.0

2.0

1.5

1.0

 

bhp

1.48

1.56

1.64

1.71

1.80

1.88

2.00

2.03

2.12

2.19

2.27

2.35

2.43

2.52

2.61

2.69

2.78

2.86

2.93

4000

Sheave/Motor

A

A

A

A

A

C

E

E

E

E

E

E

E

E

E

D

E

E

E

rpm

740

768

792

816

840

864

888

908

932

952

976

996

1016

1036

1056

1076

1096

1116

1132

 

 

Turns Open

3.5

3.0

2.5

2.0

1.5

6.0

5.5

5.0

4.5

4.5

4.0

3.5

3.5

3.0

2.5

2.5

2.0

2.0

1.5

LEGEND

bhp — Brake Horsepower ESP — External Static Pressure

NOTES:

1.A = Standard RPM/Standard Motor, B = Low RPM/Standard Motor, C = High RPM/Standard Motor, E = High RPM/Large Motor

2.Unit shipped with standard drive package with drive sheave 2.5 turns open unless otherwise requested. Field adjustment may be required for specified CFM.

3.ISO/AHRI rating point with standard drive package and drive sheave open 3.0 turns at .30 ESP.

4.Performance data does not include drive losses and is based on sea level conditions.

5.All airflow is rated at lowest voltage if unit is dual rated, i.e., rated at 208 volts for 208-230 volt units.

16

Page 16