Carrier 50RTP03-20 specifications Troubleshooting, FP1 and FP2 Thermistor Location

Models: 50RTP03-20

1 60
Download 60 pages 32.92 Kb
Page 47
Image 47
TROUBLESHOOTING

TROUBLESHOOTING

When troubleshooting problems with a WSHP, consider the cuases and solutions in Table 21.

Thermistor — A thermistor may be required for single- phase units where starting the unit is a problem due to low voltage.

Control Sensors — The control system employs 2 nom- inal 10,000 ohm thermistors (FP1 and FP2) that are used for freeze protection. Be sure FP1 is located in the discharge fluid and FP2 is located in the air discharge. See Fig. 25.

AIRFLOW

(°F)

THERMISTOR

AIR

COIL

AIRFLOW

(°F)

EXPANSION

VALVE

FP2FP1

COAX

Fig. 25 — FP1 and FP2 Thermistor Location SUCTION

COMPRESSOR

DISCHARGE

CONDENSATE

 

 

 

 

 

 

 

 

 

 

OVERFLOW

LIQUID

 

 

 

 

 

 

 

 

(CO)

 

 

 

 

LINE

WATER IN

WATER OUT

 

AIR COIL

 

WATER

 

 

 

 

FREEZE

 

 

 

 

PROTECTION

COIL

 

 

 

 

 

PROTECTION

 

 

LEGEND

COAX — Coaxial Heat Exchanger

Airflow

Refrigerant Liquid Line Flow

Fig. 25 — FP1 and FP2 Thermistor Location