Carrier 50RTP03-20 specifications Electrical Data

Models: 50RTP03-20

1 60
Download 60 pages 32.92 Kb
Page 10
Image 10
Table 3 — Electrical Data

Example: Supply voltage is 460-3-60.

AB = 452 volts

BC = 464 volts

AC = 455 volts

Average Voltage =

452 + 464 + 455

3

 

=

1371

 

3

= 457

Determine maximum deviation from average voltage: (AB) 457 – 452 = 5 v

(BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v Maximum deviation is 7 v.

Determine percent voltage imbalance.

% Voltage Imbalance = 100 x

7

457

= 1.53%

 

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electri- cal components.

NOTE: If more than 2% voltage imbalance is present, contact local electric utility.

208-VOLT OPERATION — All 208-230 volt units are factory wired for 208 volts. The transformers may be switched to 230-volt operation (as illustrated on the wiring diagram) by switching the red (208 volt) wire with the orange (230 volt) wire at the L1 terminal.

BLOWER SELECTION — All water source heat pumps are factory set with the appropriate motor and sheave combination to achieve the desired airflow performance. Performance is selected by matching the desired performance with the appro- priate region in Tables 4-12.

NOTE: Factory-installed sheaves are field adjustable. Refer to Tables 4-12 for adjustment points.

Table 3 — Electrical Data

50RTP

VOLTAGE

VOLTAGE

MIN/MAX

BLOWER

 

COMPRESSOR

 

MOTOR

 

TOTAL

 

MAX

 

 

 

 

 

 

 

 

UNIT

MCA

FUSE/

UNIT SIZE

CODE

(V-Ph-Hz)

VOLTAGE

OPTION

Qty

 

RLA

LRA

Qty

FLA

 

Hp

 

 

FLA

 

HACR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

208-3-60

197/254

A,B,C

1

 

10.4

73.0

1

4.0

 

1.0

14.4

17.0

25

03

6

460-3-60

414/506

A,B,C

1

 

5.8

38.0

1

2.0

 

1.0

7.8

9.3

15

 

1

575-3-60

518/633

A,B,C

1

 

3.8

36.5

1

1.4

 

1.0

5.2

6.2

15

 

5

208-3-60

197/254

A,B,C

1

 

13.7

83.1

1

4.0

 

1.0

17.7

21.1

35

 

D,E

1

 

13.7

83.1

1

5.0

 

1.5

18.7

22.1

35

 

 

 

 

 

 

04

6

460-3-60

414/506

A,B,C

1

 

6.2

41.0

1

2.0

 

1.0

8.2

9.8

15

D,E

1

 

6.2

41.0

1

2.4

 

1.5

8.6

10.1

15

 

 

 

 

 

 

 

1

575-3-60

518/633

A,B,C

1

 

4.8

33.0

1

1.4

 

1.0

6.2

7.4

15

 

D,E

1

 

4.8

33.0

1

1.9

 

1.5

6.7

7.9

15

 

 

 

 

 

 

 

5

208-3-60

197/254

A,B,C

1

 

15.6

110.0

1

4.0

 

1.0

19.6

23.5

40

 

D,E

1

 

15.6

110.0

1

5.0

 

1.5

20.6

24.5

40

 

 

 

 

 

 

05

6

460-3-60

414/506

A,B,C

1

 

7.8

52.0

1

2.0

 

1.0

9.8

11.8

15

D,E

1

 

7.8

52.0

1

2.4

 

1.5

10.2

12.2

15

 

 

 

 

 

 

 

1

575-3-60

518/633

A,B,C

1

 

5.8

38.9

1

1.4

 

1.0

7.2

8.7

15

 

D,E

1

 

5.8

38.9

1

1.9

 

1.5

7.7

9.2

15

 

 

 

 

 

 

 

5

208-3-60

197/254

A,B,C

1

 

20.5

155.0

1

5.0

 

1.5

25.5

30.6

50

 

E

1

 

20.5

155.0

1

6.2

 

2.0

26.7

31.8

50

 

 

 

 

 

 

06

6

460-3-60

414/506

A,B,C

1

 

9.6

75.0

1

2.4

 

1.5

12.0

14.4

20

E

1

 

9.6

75.0

1

3.1

 

2.0

12.7

15.1

20

 

 

 

 

 

 

 

1

575-3-60

518/633

A,B,C

1

 

7.6

54.0

1

1.9

 

1.5

9.5

11.4

15

 

E

1

 

7.6

54.0

1

2.3

 

2.0

9.9

11.8

15

 

 

 

 

 

 

 

5

208-3-60

197/254

A,B,C

2

 

13.7

83.1

1

6.2

 

2.0

33.6

37.0

50

 

E

2

 

13.7

83.1

1

9.2

 

3.0

36.6

40.0

50

 

 

 

 

 

 

08

6

460-3-60

414/506

A,B,C

2

 

6.2

41.0

1

3.1

 

2.0

15.5

17.0

20

E

2

 

6.2

41.0

1

4.3

 

3.0

16.7

18.3

20

 

 

 

 

 

 

 

1

575-3-60

518/633

A,B,C

2

 

4.8

33.0

1

2.3

 

2.0

11.9

13.1

15

 

E

2

 

4.8

33.0

1

3.4

 

3.0

13.0

14.2

15

 

 

 

 

 

 

 

5

208-3-60

197/254

A,B,C

2

 

15.6

110.0

1

9.2

 

3.0

40.4

44.3

60

 

E

2

 

15.6

110.0

1

14.1

 

5.0

45.3

49.2

60

 

 

 

 

 

 

10

6

460-3-60

414/506

A,B,C

2

 

7.8

52.0

1

4.3

 

3.0

19.9

21.9

25

E

2

 

7.8

52.0

1

7.0

 

5.0

22.6

24.6

30

 

 

 

 

 

 

 

1

575-3-60

518/633

A,B,C

2

 

5.8

38.9

1

3.4

 

3.0

15.0

16.5

20

 

E

2

 

5.8

38.9

1

5.2

 

5.0

16.8

18.3

20

 

 

 

 

 

 

 

5

208-3-60

197/254

A,B,C

2

 

20.5

155.0

1

9.2

 

3.0

50.2

55.3

80

 

D,E

2

 

20.5

155.0

1

14.1

 

5.0

55.1

60.2

80

 

 

 

 

 

 

12

6

460-3-60

414/506

A,B,C

2

 

9.6

75.0

1

4.3

 

3.0

23.5

25.9

35

D,E

2

 

9.6

75.0

1

7.0

 

5.0

26.2

28.6

35

 

 

 

 

 

 

 

1

575-3-60

518/633

A,B,C

2

 

7.6

54.0

1

3.4

 

3.0

18.6

20.5

25

 

D,E

2

 

7.6

54.0

1

5.2

 

5.0

20.4

22.3

25

 

 

 

 

 

 

10

Page 10
Image 10
Carrier 50RTP03-20 specifications Electrical Data