Table 18 — Complete C Control Current LED

Status and Alarm Relay Operations

LED STATUS

 

DESCRIPTION OF OPERATION

ALARM RELAY

 

 

 

Normal Mode

Open

 

On

 

Normal Mode with

Cycle

 

 

 

PM Warning

(closed 5 sec.,

 

 

 

Open 25 sec.)

 

 

 

 

 

Off

 

Control is non-functional

Open

Slow Flash

 

Fault Retry

Open

 

Fast Flash

 

Lockout

Closed

Slow Flash

 

 

Open

 

Over/Under Voltage Shutdown

(Closed after

 

 

 

 

15 minutes)

Flashing Code 1

Test Mode — No fault in memory

Cycling Code 1

Flashing Code 2

Test Mode — HP Fault in memory

Cycling Code 2

Flashing Code 3

Test Mode — LP Fault in memory

Cycling Code 3

Flashing Code 4

Test Mode — FP1 Fault in memory

Cycling Code 4

Flashing Code 5

Test Mode — FP2 Fault in memory

Cycling Code 5

Flashing Code 6

Test Mode — CO Fault in memory

Cycling Code 6

Flashing Code 7

 

Test Mode — Over/Under

Cycling Code 7

 

shutdown in memory

 

 

 

 

Flashing Code 8

 

Test Mode — PM in memory

Cycling Code 8

Flashing Code 9

 

Test Mode — Test Mode — FP1/

Cycling Code 9

 

FP2 Swapped Fault in memory

 

 

 

 

 

LEGEND

 

 

CO

Condensate Overflow

 

FP

Freeze Protection

 

HP

High Pressure

 

LED — Light-Emitting Diode

 

LP

Low Pressure

 

PM

Performance Monitor

 

NOTES:

1.Slow flash is 1 flash every 2 seconds.

2.Fast flash is 2 flashes every 1 second.

3.EXAMPLE: “Flashing Code 2” is represented by 2 fast flashes followed by a 10-second pause. This sequence will repeat continually until the fault is cleared.

Table 19 — Complete C Control LED Code and

Fault Descriptions

 

LED

FAULT

DESCRIPTION

CODE

 

 

 

1

No fault in memory

There has been no fault since

 

 

 

the last power-down to power-up

 

 

 

sequence

 

2

High-Pressure Switch

HP Open Instantly

 

3

Low-Pressure Switch

LP open for 30 continuous sec-

 

 

 

onds before or during a call

 

 

 

(bypassed for first 60 seconds)

 

4

Freeze Protection Coax

FP1 below Temp limit for 30 con-

 

 

— FP1

tinuous seconds (bypassed for

 

 

 

first 60 seconds of operation)

 

5

Freeze Protection Air Coil

FP2 below Temp limit for 30 con-

 

 

— FP2

tinuous seconds (bypassed for

 

 

 

first 60 seconds of operation)

 

6

Condensate overflow

Sense overflow (grounded) for

 

 

 

30 continuous seconds

 

7

Over/Under Voltage

"R" power supply is <19VAC or

(Autoreset)

Shutdown

>30VAC

 

8

PM Warning

Performance Monitor Warning

 

 

 

has occurred.

 

9

FP1 and FP2 Thermistors

FP1 temperature is higher than

 

 

are Swapped

FP2 in heating/test mode, or FP2

 

 

 

temperature is higher than FP1

 

 

 

in cooling/test mode.

 

LEGEND

 

FP

Freeze Protection

 

HP

High Pressure

 

LED — Light-Emitting Diode

 

LP

Low Pressure

 

PM

Performance Monitor

 

Table 20 — Aquazone™ Deluxe D Control Current LED Status and Alarm Relay Operations

DESCRIPTION

STATUS LED

TEST LED

FAULT LED (Red)

ALARM RELAY

(Green)

(Yellow)

 

 

 

Normal Mode

On

Off

Flash Last Fault Code in Memory

Open

Normal Mode with PM

On

Off

Flashing Code 8

Cycle (closed 5 sec,

open 25 sec, …)

 

 

 

 

Deluxe D Control is

Off

Off

Off

Open

non-functional

 

 

 

 

Test Mode

On

Flash Last Fault Code in Memory

Cycling Appropriate Code

Night Setback

Flashing Code 2

Flash Last Fault Code in Memory

ESD

Flashing Code 3

Flash Last Fault Code in Memory

Invalid T-stat Inputs

Flashing Code 4

Flash Last Fault Code in Memory

No Fault in Memory

On

Off

Flashing Code 1

Open

HP Fault

Slow Flash

Off

Flashing Code 2

Open

LP Fault

Slow Flash

Off

Flashing Code 3

Open

FP1 Fault

Slow Flash

Off

Flashing Code 4

Open

FP2 Fault

Slow Flash

Off

Flashing Code 5

Open

CO Fault

Slow Flash

Off

Flashing Code 6

Open

Over/Under Voltage

Slow Flash

Off

Flashing Code 7

Open (closed after 15 minutes)

HP Lockout

Fast Flash

Off

Flashing Code 2

Closed

LP Lockout

Fast Flash

Off

Flashing Code 3

Closed

FP1 Lockout

Fast Flash

Off

Flashing Code 4

Closed

FP2 Lockout

Fast Flash

Off

Flashing Code 5

Closed

CO Lockout

Fast Flash

Off

Flashing Code 6

Closed

LEGEND

CO — Condensate Overflow

ESD — Emergency Shutdown

FP — Freeze Protection

HP — High Pressure

LP — Low Pressure

PM — Performance Monitor

NOTES:

1.If there is no fault in memory, the Fault LED will flash code 1.

2.Codes will be displayed with a 10-second Fault LED pause.

3.Slow flash is 1 flash every 2 seconds.

4.Fast flash is 2 flashes every 1 second.

5.EXAMPLE: “Flashing Code 2” is represented by 2 fast flashes fol- lowed by a 10-second pause. This sequence will repeat continually until the fault is cleared.

44

Page 44
Image 44
Carrier 50RTP03-20 specifications Complete C Control LED Code Fault Descriptions