Table 18 — Complete C Control Current LED
Status and Alarm Relay Operations
LED STATUS |
| DESCRIPTION OF OPERATION | ALARM RELAY | |
|
|
| Normal Mode | Open |
| On |
| Normal Mode with | Cycle |
|
|
| PM Warning | (closed 5 sec., |
|
|
| Open 25 sec.) | |
|
|
|
| |
| Off |
| Control is | Open |
Slow Flash |
| Fault Retry | Open | |
| Fast Flash |
| Lockout | Closed |
Slow Flash |
|
| Open | |
| Over/Under Voltage Shutdown | (Closed after | ||
|
|
|
| 15 minutes) |
Flashing Code 1 | Test Mode — No fault in memory | Cycling Code 1 | ||
Flashing Code 2 | Test Mode — HP Fault in memory | Cycling Code 2 | ||
Flashing Code 3 | Test Mode — LP Fault in memory | Cycling Code 3 | ||
Flashing Code 4 | Test Mode — FP1 Fault in memory | Cycling Code 4 | ||
Flashing Code 5 | Test Mode — FP2 Fault in memory | Cycling Code 5 | ||
Flashing Code 6 | Test Mode — CO Fault in memory | Cycling Code 6 | ||
Flashing Code 7 |
| Test Mode — Over/Under | Cycling Code 7 | |
| shutdown in memory | |||
|
|
|
| |
Flashing Code 8 |
| Test Mode — PM in memory | Cycling Code 8 | |
Flashing Code 9 |
| Test Mode — Test Mode — FP1/ | Cycling Code 9 | |
| FP2 Swapped Fault in memory | |||
|
|
|
| |
| LEGEND |
|
| |
CO | — Condensate Overflow |
| ||
FP | — Freeze Protection |
| ||
HP | — High Pressure |
| ||
LED — |
| |||
LP | — Low Pressure |
| ||
PM | — Performance Monitor |
|
NOTES:
1.Slow flash is 1 flash every 2 seconds.
2.Fast flash is 2 flashes every 1 second.
3.EXAMPLE: “Flashing Code 2” is represented by 2 fast flashes followed by a
Table 19 — Complete C Control LED Code and
Fault Descriptions
| LED | FAULT | DESCRIPTION | |
CODE | ||||
|
| |||
| 1 | No fault in memory | There has been no fault since | |
|
|
| the last | |
|
|
| sequence | |
| 2 | HP Open Instantly | ||
| 3 | LP open for 30 continuous sec- | ||
|
|
| onds before or during a call | |
|
|
| (bypassed for first 60 seconds) | |
| 4 | Freeze Protection Coax | FP1 below Temp limit for 30 con- | |
|
| — FP1 | tinuous seconds (bypassed for | |
|
|
| first 60 seconds of operation) | |
| 5 | Freeze Protection Air Coil | FP2 below Temp limit for 30 con- | |
|
| — FP2 | tinuous seconds (bypassed for | |
|
|
| first 60 seconds of operation) | |
| 6 | Condensate overflow | Sense overflow (grounded) for | |
|
|
| 30 continuous seconds | |
| 7 | Over/Under Voltage | "R" power supply is <19VAC or | |
(Autoreset) | Shutdown | >30VAC | ||
| 8 | PM Warning | Performance Monitor Warning | |
|
|
| has occurred. | |
| 9 | FP1 and FP2 Thermistors | FP1 temperature is higher than | |
|
| are Swapped | FP2 in heating/test mode, or FP2 | |
|
|
| temperature is higher than FP1 | |
|
|
| in cooling/test mode. | |
| LEGEND |
| ||
FP | — Freeze Protection |
| ||
HP | — High Pressure |
| ||
LED — |
| |||
LP | — Low Pressure |
| ||
PM | — Performance Monitor |
|
Table 20 — Aquazone™ Deluxe D Control Current LED Status and Alarm Relay Operations
DESCRIPTION | STATUS LED | TEST LED | FAULT LED (Red) | ALARM RELAY | |
(Green) | (Yellow) | ||||
|
|
| |||
Normal Mode | On | Off | Flash Last Fault Code in Memory | Open | |
Normal Mode with PM | On | Off | Flashing Code 8 | Cycle (closed 5 sec, | |
open 25 sec, …) | |||||
|
|
|
| ||
Deluxe D Control is | Off | Off | Off | Open | |
| |||||
|
|
|
| ||
Test Mode | — | On | Flash Last Fault Code in Memory | Cycling Appropriate Code | |
Night Setback | Flashing Code 2 | — | Flash Last Fault Code in Memory | — | |
ESD | Flashing Code 3 | — | Flash Last Fault Code in Memory | — | |
Invalid | Flashing Code 4 | — | Flash Last Fault Code in Memory | — | |
No Fault in Memory | On | Off | Flashing Code 1 | Open | |
HP Fault | Slow Flash | Off | Flashing Code 2 | Open | |
LP Fault | Slow Flash | Off | Flashing Code 3 | Open | |
FP1 Fault | Slow Flash | Off | Flashing Code 4 | Open | |
FP2 Fault | Slow Flash | Off | Flashing Code 5 | Open | |
CO Fault | Slow Flash | Off | Flashing Code 6 | Open | |
Over/Under Voltage | Slow Flash | Off | Flashing Code 7 | Open (closed after 15 minutes) | |
HP Lockout | Fast Flash | Off | Flashing Code 2 | Closed | |
LP Lockout | Fast Flash | Off | Flashing Code 3 | Closed | |
FP1 Lockout | Fast Flash | Off | Flashing Code 4 | Closed | |
FP2 Lockout | Fast Flash | Off | Flashing Code 5 | Closed | |
CO Lockout | Fast Flash | Off | Flashing Code 6 | Closed |
LEGEND
CO — Condensate Overflow
ESD — Emergency Shutdown
FP — Freeze Protection
HP — High Pressure
LP — Low Pressure
PM — Performance Monitor
NOTES:
1.If there is no fault in memory, the Fault LED will flash code 1.
2.Codes will be displayed with a
3.Slow flash is 1 flash every 2 seconds.
4.Fast flash is 2 flashes every 1 second.
5.EXAMPLE: “Flashing Code 2” is represented by 2 fast flashes fol- lowed by a