DO NOT store or install units in corrosive environments or in locations subject to temperature or humidity extremes (e.g., attics, garages, rooftops, etc.). Corrosive conditions and high temperature or humidity can significantly reduce performance, reliability, and service life. Always move units in an upright position. Tilting units on their sides may cause equipment damage.

Manual background CAUTION

DO NOT store or install units in corrosive environments or in locations subject to temperature or humidity extremes (e.g., attics, garages, rooftops, etc.). Corrosive conditions and high temperature or humidity can significantly reduce performance, reliability, and service life. Always move units in an upright position. Tilting units on their sides may cause equipment damage.

INSPECT UNIT — To prepare the unit for installation, com- plete the procedures listed below:

1.Compare the electrical data on the unit nameplate with ordering and shipping information to verify that the correct unit has been shipped.

2.Verify that the unit is the correct model for the entering water temperature of the job.

3.Do not remove the packaging until the unit is ready for installation.

4.Verify that the refrigerant tubing is free of kinks or dents, and that it does not touch other unit components.

5.Inspect all electrical connections. Be sure connections are clean and tight at the terminals.

6.Compressors are internally spring-mounted. Compressors equipped with external spring vibration isolators must have bolts loosened and shipping clamps removed.

7.Remove any blower support cardboard from inlet of the blower if present.

8.Locate and verify any accessory kit located in compressor section.

9.Remove any access panel screws that may be difficult to remove once unit is installed.

Step 3 — Locate Unit — The following guidelines should be considered when choosing a location for WSHP. Re- fer to Fig. 1-3 for unit dimensional data. See Fig. 4 for accesso- ry roof curb dimensional data.

Provide sufficient space for water, electrical and duct connections

Locate unit in an area that allows for easy access and removal of filter and access panels

Allow enough space for service personnel to perform maintenance

Table 1 — Physical Data — Aquazone™ 50RTP03-20 Units

UNIT 50RTP

03

 

04

 

05

 

06

 

08

 

10

 

12

 

14

 

20

Compressor (qty)

 

 

 

Scroll (1)

 

 

 

 

 

 

 

Scroll (2)

 

 

 

 

Factory Charge R-410A (oz)

64

 

84

 

120

 

132

 

108

 

120

 

130

 

192

 

300

Blower Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor Quantity

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

Standard Motor (hp)

1

 

1

 

1

 

1.5

 

2

 

3

 

3

 

3

 

5

Large Motor (hp)

N/A

 

1.5

 

1.5

 

2

 

3

 

5

 

5

 

5

 

7.5

Blower(s)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Number of Blowers

 

 

 

 

 

1

 

 

 

 

 

 

 

 

2

Blower Wheel Size (dia x w)

10 x 6

 

 

 

2 x 12

 

15 x 11

 

15 x 15

 

 

15 x 11

V-belt size, Std drive

A29

 

A30

 

A32

 

AX33

 

B40

 

BX42

 

BX46

 

B39

 

BX40

Water Connection Size

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IPT (in.)

3/4

 

 

1

 

11/4

 

 

11/2

 

 

 

 

2

Coax Volume

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Volume (US Gallons)

0.61

 

0.77

 

1.11

 

1.30

 

1.69

 

2.29

 

2.68

 

3.83

 

4.77

 

 

 

 

 

 

 

 

Condensate Connection Size

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FPT (in.)

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

Air Coil Data

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air Coil Total Face Area (sq ft)

5

 

 

 

7

 

9.33

 

 

10.5

 

 

20

Filter, Standard, Qty...Size (in.)

 

 

4...16 x 20

 

 

 

 

 

6...16 x 20

 

8...16 x 20,

 

 

 

 

 

 

 

 

2...20 x 20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operating Weight (lb)

735

 

785

 

835

 

880

 

1080

 

1125

 

1175

 

1770

 

1960

Shipping Weight (lb)

750

 

800

 

850

 

900

 

1100

 

1150

 

1200

 

1800

 

2000

Corner Weights (lb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Front-Left

184

 

196

 

208.5

 

224

 

292

 

303.5

 

320

 

479

 

530

Front-Right

259

 

276

 

293.5

 

298

 

380

 

395.5

 

406

 

623

 

690

Rear-Left

108.5

 

117

 

124.5

 

134

 

193

 

202

 

212.5

 

315

 

350

Rear-Right

183.5

 

196

 

208.5

 

224

 

215

 

224

 

236.5

 

353

 

390

Curb, Installed (lb)

 

 

 

83

 

 

 

 

94

 

 

 

 

128

IPT — Iron (National) Pipe Thread

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

Page 3
Image 3