Page 24
Image 24

5.Reconnect the cabling and confirm the faults clear.

6.Final testing and commissioning of the loop through to the fire protection equipment, including test [simulated] activation of the equipment, should be carried out at the appropriate time in conjunction with the engineer responsible for the fire protection system.

13.7.6Commissioning ancillary inputs

Remote Silence Alarms, Reset and Evacuate inputs should each be tested by the activation of the remote equipment. The response should be verified for each signal.

13.7.7Commissioning ancillary outputs

The correct operation of equipment connected to the Zone Outputs, Disablement Active, Evacuate Active and Buzzer Active outputs should be verified in turn by initiating a fire condition on each of the appropriate zones; disabling/enabling a zone; operating the Evacuate button on the panel’s display.

13.7.8Commissioning repeaters

1.Power-up the Panel and then the Repeaters. Only the “Power Supply On” LEDs should be illuminated on the Panel and Repeaters.

2.At Repeater 1, turn the Access control switch to “1”, and press the “Evacuate” button. Check that the alarms operate and the internal buzzer operates on all repeaters.

3.Press the “Silence” button on the fire alarm panel. Check that the alarm circuits silence and the internal buzzer silences on all repeaters.

4.Repeat steps 2 and 3 for each repeater.

5.Operate a Manual Call Point on zone 1 and check for correct fire indication at each repeater.

6.Press the “Silence Alarms” button on a repeater and check that the alarms are silenced and the Zone 1 fire LED is constantly illuminated on all repeater panels.

7.Press the “Reset” button on a repeater and check that the panel and repeaters return to the quiescent state.

8.Repeat steps 5 to 7 for each zone and ensure “Silence Alarms” and “Reset” operate correctly from each repeater.

9.Set the DIL switches on the C1631 Repeater Interface card in the fire alarm panel OFF (No Repeaters). Check that all repeaters indicate a “Comms. Fault”.

10.Set the C1631 Repeater Interface card DIL switches in the fire alarm panel back to their previous settings and check that the repeaters return to normal.

11.Set the first repeater address to 0. Check that the panel indicates a “Repeater fault” and any additional repeaters display a steady “Comms fault” LED.

12.Set the first repeater address back to normal and check that the panel and repeaters return to normal.

13.Repeat steps 11 and 12 for any other connected repeaters.

Page 24 of 40

Page 24
Image 24
BRK electronic Mx-1000 manual Commissioning ancillary inputs, Commissioning ancillary outputs, Commissioning repeaters

Mx-1000 specifications

The BRK electronic Mx-1000 is an innovative and versatile device designed for both home and industrial use, primarily focusing on smoke and carbon monoxide detection. Its advanced features enhance safety, ensuring peace of mind for users in various environments.

One of the standout features of the Mx-1000 is its dual-sensor technology. It combines both photoelectric and ionization sensors, maximizing its ability to detect different types of smoke. Photoelectric sensors are highly effective at identifying smoldering fires, which are often associated with slow-burning materials. On the other hand, ionization sensors excel at detecting fast-flaming fires. This dual capability ensures comprehensive fire detection, making the Mx-1000 one of the most reliable devices in its category.

Another notable characteristic is its built-in carbon monoxide detector. Carbon monoxide is a silent killer, and the Mx-1000 addresses this threat by providing early warning signals when harmful levels of this gas are detected. The integration of both smoke and carbon monoxide detection in a single unit simplifies safety measures and reduces the number of devices required for home and workplace safety.

The Mx-1000 is equipped with advanced digital technology that enhances its functionality. A state-of-the-art microprocessor evaluates alarm conditions more intelligently, which minimizes the chances of false alarms. This feature is particularly beneficial for households that might experience frequent smoke triggers from cooking or other benign sources.

User-friendliness is a key design aspect of the Mx-1000. It features a clear LED display that indicates the operational status, and a simple test button allows users to verify functionality with ease. The device also features a low-battery indicator, ensuring users are always informed about its operational state.

Installation is straightforward, with options for both wall and ceiling mounting to accommodate various room layouts. The Mx-1000 is designed to appeal to a wide range of customers, from DIY enthusiasts to professional installers.

In addition to its technological advancements, the BRK electronic Mx-1000 is built with reliability in mind. Its durable construction is meant to endure various conditions, ensuring longevity and consistent performance over time. This combination of top-tier technology, user-friendly features, and robust design makes the Mx-1000 a trusted choice for those seeking comprehensive safety solutions in smoke and carbon monoxide detection.