![](/images/new-backgrounds/1058313/5831321x1.webp)
COLLECTOR BOX |
DRAIN TUBE (BLUE) |
PLUG |
CAP |
COLLECTOR BOX |
TUBE (GREEN) |
COLLECTOR BOX |
TUBE (PINK) |
COLLECTOR BOX |
DRAIN TUBE (BLUE & |
WHITE STRIPED) |
COLLECTOR BOX |
TUBE EXTENSION |
CONDENSATE |
TRAP |
INDUCER HOUSING |
(MOLDED) DRAIN |
TUBE (VIOLET) |
DRAIN TUBE |
COUPLING |
COLLECTOR BOX
TUBE (GREEN)
CAP
COLLECTOR BOX
DRAIN TUBE (BLUE)
COLLECTOR BOX
TUBE (PINK)
PLUG
COLLECTOR BOX DRAIN TUBE (BLUE & WHITE STRIPED)
COLLECTOR BOX
TUBE EXTENSION
INDUCER HOUSING (MOLDED) DRAIN TUBE (VIOLET)
CONDENSATE
TRAP
COLLECTOR BOX
EXTENSION
DRAIN TUBE
355CAV
A07276
Fig. 9 - Downflow Tube Configuration
(Left-hand Trap Installation)
DOWNFLOW APPLICATIONS
A downflow furnace application is where furnace blower is located above combustion and controls section of furnace, and conditioned air is discharged downwards.
Condensate Trap Location
The condensate trap must be removed from the
To relocate condensate trap from the blower shelf to desired location, perform the following:
1.Remove three tubes connected to condensate trap.
2.Remove trap from blower shelf by gently pushing tabs in- ward and rotating trap.
3.Remove casing hole filler cap from casing hole. (See Fig. 2 and 10.)
4.Install casing hole filler cap
!WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
Casing hole filler cap must be installed in blower shelf hole when condensate trap is relocated to prevent combustion products being drawn in from appliances in the equipment room.
5.Install condensate trap into
6.Fill unused condensate trap casing holes with plastic filler caps
A07277
Fig. 10 - Downflow Tube Configuration
(Right-Hand Trap Configuration)
Condensate Trap Tubing
NOTE: See Fig. 9 or 10 or tube routing label on main furnace door to check for proper connections.
1.Collector Box Drain Tube
a.Remove
b.Install removed clamp and plug into UPPER collector box drain tube (blue label) which was connected to con- densate trap.
c.Connect LOWER collector box drain connection to con- densate trap.
(3.) Condensate Trap Located on Left Side of Casing
(a.)Connect LOWER collector box drain tube (blue and white striped label) to condensate trap. Tube does not need to be cut.
(b.)Clamp tube to prevent any condensate leakage. (4.) Condensate Trap Located on Right Side of Casing
(a.)Install drain tube coupling
(b.)Connect larger diameter drain tube
(c.)Route extended collector box drain tube between gas valve and inlet housing as shown in Fig. 10.
(d.)Determine appropriate length and cut. (e.)Connect to condensate trap.
2.Inducer Housing Drain Tube
a.Remove
11