3.Caulking or sealants are applied to areas such as joints around window and door frames; between sole plates and floors; between wall-ceiling joints; between wall panels; at penetrations for plumbing, electrical, and fuel lines; and at other openings.

If combustion and ventilation air must be supplied to an uncon- fined space from outside, an opening with a FREE AREA of not less than 1 sq in. per 1000 Btuh of total input of all appliances within unconfined space (but not less than 100 sq in.) must be provided. This opening must be located such that it can not be blocked at any time.

When furnace is installed in a closet or enclosure, 2 ventilation openings, with OPEN AREA as dimensioned in example below are required for combustion air. The openings should be located about 6 in. from top and bottom of enclosure at front of furnace.

For Example:

UNIT

LENGTH

HEIGHT

SIZE

(IN.)

(IN.)

036105

18

9

048125

20

10

060155

20

10

 

 

 

For a confined space, where air is taken from an interior space, 2 permanent openings of equal area are required. One opening must be within 12 in. of ceiling and the other within 12 in. of floor. Each opening must have a free area of at least 1 sq in. per 1000 Btuh of total input rating but not less than 100 sq in.

If outside air is supplied to a confined space, then the 2 openings must be equal and located as above. The free area of each must be:

1.One sq in. per 4000 Btuh of total input rating when air is directly communicated from outdoors.

2.One sq in. per 4000 Btuh of total input rating when air is brought in through vertical ducts.

3.One sq in. per 2000 Btuh of total input rating when air is transferred through horizontal ducts.

When ducts are used to supply air, they must be of the same cross sectional area as free area of openings to which they connect.

The minimum dimension of rectangular air ducts must not be less than 3 in.

In calculating free area, consideration shall be given to blocking effect of louvers, grilles, or screens protecting openings. Screens used shall not be smaller than 1/4-in. mesh and shall be readily accessible for cleaning. If free area through a design of louver or grille is known, it shall be used in calculating size design and free area specified. If design and free area are not known, it may be assumed that wood louvers have 20 percent free area and metal louvers and grilles have 60 percent free area. Louvers shall be fixed in open position or interlocked with furnace so they open automatically at furnace start-up and remain open during furnace operation.

WARNING: Do not block combustion-air openings in the furnace. Any blockage will result in improper com- bustion which may result in a fire hazard and/or cause bodily harm.

The lack of a proper amount of combustion air can lead to serious furnace operational problems. Some of these problems are:

1.Excessive oil burner after drip and oil fumes.

2.Sooting.

3.Melted oil burner couplings and/or ignitor/relay control.

4.A condition where air band or air shutter settings must be more open than normal to achieve proper combustion.

Ð3Ð

5.Lockouts on start-up.

II. DUCT WORK RECOMMENDATIONS

The proper sizing of warm air ducts is necessary to ensure satisfactory furnace operation. Duct work should be in accordance with the latest editions of NFPA-90A (Installation of Air Condi- tioning and Ventilating Systems) and NFPA-90B (Warm Air Heating and Air Conditioning Systems) or Canadian equivalent.

The supply duct work should be attached to flanged opening provided at discharge end of furnace. See Fig. 5 for dimensions of this opening.

The following recommendations should be followed when install- ing duct work:

1.Install locking-type dampers in all branches of individual ducts to balance out system. Dampers should be adjusted to impose proper static at outlet of furnace.

2.A flexible duct connector of noncombustible material should be installed at unit on both supply- and return-air systems. In applications where extremely quiet operation is necessary, the first 10 ft (if possible) of supply and return ducts should be internally lined with acoustical material.

3.In cases where return-air grille is located close to fan inlet, there should be at least one 90° air turn between fan inlet and grille. Further reduction in sound level can be accom- plished by installing acoustical air turning vanes or lining duct as described in item 2 above.

4.When a single air grille is used, duct between grille and furnace must be the same size as return opening in furnace.

CAUTION: Return-air grilles and warm air registers MUST not be obstructed.

WARNING: When supply ducts carry air circulated by furnace to areas outside spaces containing furnace, return air MUST also be handled by a duct sealed to furnace casing and terminating outside space containing furnace. Incorrect duct work termination and sealing will create a hazardous condition which could lead to bodily harm.

When installing furnace with cooling equipment for year-round operation, the following recommendations must be followed for series or parallel airflow:

1.In series airflow applications, coil is mounted after furnace in an enclosure in supply-air stream. The furnace blower is used for both heating and cooling airflow.

WARNING: The coil MUST be installed on air dis- charge side of furnace. Under no circumstances should airflow be such that cooled, conditioned air can pass over furnace heat exchanger. This will cause condensation in heat exchanger and possible failure of heat exchanger which could lead to a fire hazard and/or a hazardous condition which may lead to bodily harm. Heat exchanger failure due to improper installation may not be covered by warranty.

2.In parallel airflow applications, dampers must be provided to direct air over furnace heat exchanger when heat is desired and over cooling coil when cooling is desired.

IMPORTANT: The dampers should be adequate to prevent cooled air from entering furnace. If manually operated, dampers must be equipped with a means to prevent operation of either cooling unit or furnace unless damper is in full cool or heat position.

Page 3
Image 3
Bryant 362AAN instruction manual Ð3Ð, Lockouts on start-up, II. Duct Work Recommendations

362AAN specifications

The Bryant 362AAN is an exemplary air conditioning unit renowned for its durability, efficiency, and advanced technology. Designed to cater to both residential and light commercial applications, the 362AAN stands out as a highly reliable solution for cooling needs.

One of the main features of the Bryant 362AAN is its high-efficiency performance. With SEER ratings reaching as high as 16, this unit can significantly reduce energy costs while providing optimal cooling. The 362AAN employs a two-stage cooling system that enhances comfort by maintaining a more consistent indoor temperature. This feature not only ensures a pleasant environment but also helps in saving energy by adjusting the cooling output according to the indoor conditions.

The Bryant 362AAN is built using high-quality materials and components, ensuring reliability and longevity. Its all-aluminum coil enhances corrosion resistance, making it suitable for various climates. This durability extends the unit's lifespan and reduces the need for frequent repairs or replacements, providing homeowners with peace of mind.

A standout technology in the Bryant 362AAN is the EcoNet Smart Thermostat compatibility, which allows users to monitor and control their cooling system remotely. This smart technology provides real-time data, enabling users to optimize energy consumption and receive alerts for maintenance needs. The integration of smart technology also allows for potential energy savings, as users can customize their cooling schedules based on their lifestyle.

Noise reduction is another key characteristic of the Bryant 362AAN. Designed with advanced sound technology, this unit operates at quieter levels, ensuring minimal disruption to indoor activities. This is particularly beneficial in residential areas where noise can be a concern.

In terms of installation versatility, the Bryant 362AAN can be easily integrated into various home setups. Its compact design and flexible installation options ensure that it can fit in tight spaces without compromising performance.

Overall, the Bryant 362AAN air conditioning unit combines efficiency, technology, and reliability to provide an outstanding cooling solution. With its range of features and commitment to sustainability, it remains a popular choice among homeowners and businesses looking to enhance their indoor comfort while minimizing energy consumption.