Bryant 502A manual Guide Specifications, Indoor Packaged Unit, PART 1 - GENERAL, PART 2 - PRODUCTS

Models: 502A

1 16
Download 16 pages 5.03 Kb
Page 15
Image 15

GUIDE SPECIFICATIONS

INDOOR PACKAGED UNIT

HVAC GUIDE SPECIFICATIONS — SECTION 15787

SIZE RANGE: 2 TO 5 TONS, NOMINAL

BRYANT MODEL NUMBER: 502A

C.Fans:

1.Evaporator:

a.Blower shall be of the forward-curved, centrifugal, direct-drive type or belt drive (4 and 5 tons only).

PART 1 — GENERAL

b. Motor

shall

have

permanently

lubricated

bearings.

 

 

 

1.01 SYSTEM DESCRIPTION

 

 

 

c. Unit sizes 048, 060 shall be available with an

Indoor mounted, electrically controlled packaged horizon-

optional 1.5 hp fan motor.

 

tal cooling unit utilizing a hermetic type scroll compressor.

 

2. Condenser:

 

 

 

 

1.02 QUALITY ASSURANCE

 

 

 

 

a. Blower shall be of the forward-curved, centrifugal,

A. Unit shall be certified in accordance with ARI Stand-

direct-driven

type (024 only), or

belt drive

ard 210.

(036,048,060).

 

 

B. Unit shall be UL listed and carry a UL label.

 

 

b. Motor

shall

have

permanently

lubricated

C. Unit shall be CSA approved (except 3 ton, 3-phase units).

bearings.

 

 

 

D. Unit shall be factory run-tested to ensure proper perfor-

D. Compressor:

 

 

 

 

mance prior to delivery.

1. Fully hermetic scroll type.

 

 

 

 

 

1.03 DELIVERY, STORAGE, AND HANDLING

2. Mounted on suitable spring vibration isolators.

A. Unit shall be shipped completely assembled and ready to

operate.

3. Equipped with internal line break protection.

B. Unit

shall be shipped factory charged with refrigerant

 

E. Coils:

 

 

 

Evaporator and condenser coils shall be of non-ferrous

R-22.

 

 

 

 

 

C. Unit shall be stored and handled in accordance with the

 

construction with aluminum fins mechanically bonded to

 

seamless copper tubes with all joints brazed.

 

unit manufacturer’s instructions.

 

 

 

 

 

 

 

F. Refrigerant Components:

 

 

PART 2 — PRODUCTS

 

 

 

 

 

 

 

 

 

 

 

 

Refrigerant components shall include:

 

2.01 EQUIPMENT

 

 

 

 

 

 

 

 

 

 

 

1. Capillary tube feed system.

 

 

A. General:

 

 

 

 

 

 

 

 

 

 

 

 

2. Refrigerant filter-drier.

 

 

Factory assembled horizontal, single piece, air cooled,

 

 

 

 

G. Filter Section:

 

 

indoor, ceiling plenum mounted electric cooling unit. Con-

 

 

 

tained within the unit enclosure shall be all factory wiring,

 

Filter section shall consist of factory-installed, permanent,

piping, controls, refrigerant charge (R-22), and special

 

cleanable air filter, removable from the same side as the

features required prior to start-up.

 

 

 

access panels without the use of tools.

 

B. Unit Cabinet:

 

 

 

 

 

H. Controls and Safeties:

 

 

1.

 

Constructed of galvanized steel.

 

 

 

Control system shall include a high-pressure switch, a

2.

 

Interior shall be insulated with 1/2-in. thick neoprene

 

low-pressure switch, and a compressor lockout feature

 

 

coated fiberglass. Insulation shall be bonded to inte-

 

which upon tripping of any safety device shall prevent

 

 

rior surfaces by sprayed water reduceable adhesive.

 

compressor from restarting until reset at the thermostat

3. Equipped with 3 same side access panels and 2 bot-

 

(on all 3-phase units and 036 single-phase units only).

 

I. Operating characteristics:

 

 

 

 

tom hanging removable doors to facilitate ease of

 

 

 

 

 

maintenance. Side panels allow access to the control

 

1.

Unit shall operate using refrigerant R-22.

 

 

 

box, refrigeration components, and condenser coil.

 

2. Unit shall be designed for indoor suspended horizon-

 

 

Control box shall be hinged allowing access to the

 

 

 

 

 

tal mounting and operation.

 

 

 

 

compressor and pressure switches. Bottom doors

 

 

 

 

 

 

 

J. Electrical Requirements

 

 

 

 

shall allow access to and easy removal of the

 

 

 

 

 

condenser and evaporator motors and blower

 

Unit shall have single point power connection to leads in

 

 

assemblies.

 

 

 

 

 

terminal box.

 

 

4.

Equipped with two

3/ -in. threaded condensate drain

 

K. Special Features:

 

 

 

 

 

4

 

 

3/ -in.

 

 

 

 

 

connections below the evaporator coil and one

 

Certain standard features are not applicable when the

 

 

 

 

 

 

4

 

 

 

threaded connection for condenser coil wash down.

 

features designated by * are specified. For assistance in

 

 

Connections shall

be

factory plugged

for

field

 

 

 

 

amending the specifications, your

local Bryant

Sales

 

 

removal.

 

 

 

 

 

 

 

 

 

 

 

 

Office should be contacted.

 

 

5.

Field splittable through the removal of 4 bolts and

 

 

 

*

1.

Electric Heat Module:

 

 

 

 

extending refrigerant piping and wiring

to

allow

 

 

 

 

 

 

a. Provides encased heater

elements that

shall

 

 

remote horizontal or vertical condenser mounting.

 

 

 

 

 

 

attach directly to the base unit discharge.

 

6. Unit shall have an integral hanging bracket requiring

 

 

 

 

 

b. Shall have bottom access.

 

 

 

 

only 4 threaded rods (8 if unit is split) run to the top

 

 

 

 

 

 

 

 

 

 

 

 

 

flange of the unit for hanging, eliminating need for

 

 

c. UL listed.

 

 

 

 

external hanger brackets.

 

 

 

2. Thermostat Assembly:

 

 

7.

 

Contains junction

box

for power connection and

 

 

 

 

 

 

Provides cooling and fan control. Standard subbase

 

 

 

 

 

 

 

 

 

opening for routing of control wiring.

shall include ‘‘Compressor malfunction light’’

 

 

designed to illuminate if compressor lockout is

 

activated.

15

Page 15
Image 15
Bryant 502A manual Guide Specifications, Indoor Packaged Unit, PART 1 - GENERAL, PART 2 - PRODUCTS