CONTROLS

OPERATING SEQUENCE

Cooling

1.Thermostat calls for cooling.

a.Indoor (evaporator) fan relay is energized and starts evaporator fan.

b.Compressor contactor is energized to start compressor and condenser fan (up to a 5-minute delay on single- phase units).

2.When room thermostat is satisfied, the evaporator fan, com- pressor, and condenser fan shut off.

Continuous Fan Operation — The thermostat can be set for continuous operation by setting the fan switch to ON.

ELECTRICAL DATA

UNIT

V-PH

 

VOLTAGE RANGE

COMPRESSOR

 

FAN MOTORS

 

 

POWER SUPPLY

 

Evaporator

Condenser

 

Min Ckt

MOCP

502A

(60 Hz)

 

 

 

 

 

 

 

 

 

 

Min

Max

RLA

LRA

Hp

FLA

Hp

FLA

 

Amps

Amps

024

 

230-1

 

207

254

11.5

62.5

.17

1.10

.50

3.40

 

19.1

25

036

 

230-1

 

207

254

17.2

96.0

.50

3.20

.75

6.06

 

29.5

40

 

208/230-3

 

187

254

10.2

77.0

.50

3.20

.75

3.93

 

19.9

25

 

 

460-3

 

414

508

4.3

37.0

.50

1.50

.75

1.97

 

8.8

15

 

 

230-1

 

207

254

23.7

129.0

.75

4.00

1.0

8.35

 

42.0

60

048

 

208/230-3

 

187

254

13.5

99.0

.75

4.00

1.0

3.93

 

24.8

35

 

460-3

 

414

508

7.4

49.5

.75

2.15

1.0

1.97

 

13.4

15

 

 

 

 

 

 

575-3

 

518

632

5.8

40.0

.75

1.40

1.0

1.45

 

10.1

15

048*

 

208/230-3

 

187

254

13.5

99.0

1.5

5.60

1.0

3.93

 

26.4

35

 

460-3

 

414

508

7.4

49.5

1.5

2.80

1.0

1.97

 

14.0

20

 

 

 

 

 

 

230-1

 

207

254

28.8

169.0

.75

4.00

1.5

9.50

 

49.5

70

060

 

208/230-3

 

187

254

17.3

123.0

.75

4.00

1.5

4.82

 

30.4

45

 

460-3

 

414

508

9.0

62.0

.75

2.15

1.5

2.41

 

15.8

25

 

 

 

 

 

 

575-3

 

518

632

7.1

50.0

.75

1.40

1.5

1.90

 

12.2

20

060*

 

208/230-3

 

187

254

17.3

123.0

1.5

5.60

1.5

4.82

 

32.0

40

 

460-3

 

414

508

9.0

62.0

1.5

2.80

1.5

2.41

 

16.5

25

 

 

 

 

 

 

LEGEND

 

 

 

*Optional evaporator-fan motor nameplate data.

 

 

HACR

Heating, Air Conditioning, and Refrigeration

 

 

 

 

 

 

 

 

Hp

Horsepower

 

 

 

 

 

 

 

 

 

 

 

FLA

Full Load Amps

 

 

 

 

 

 

 

 

 

 

 

LRA

Locked Rotor Amps

 

 

 

 

 

 

 

 

 

 

MOCP — Maximum Overcurrent Protection (HACR breaker)

 

 

 

 

 

 

 

 

RLA

Rated Load Amps

 

 

 

 

 

 

 

 

 

 

ELECTRIC HEATER DATA

ELECTRIC HEATER

USED WITH

V-PH

CAP. (kW)

 

BRANCH CIRCUIT

 

UNIT 88EN

UNIT 502A

(60 Hz)

Heater Amps

MCA

 

MOCP (Amps)

 

 

0050CA01

 

240-1

5.0

20.8

26.0

 

30

0075CA01

 

240-1

7.5

31.3

39.1

 

40

0115CA01

024, 036

240-1

11.5

47.9

59.9

 

60

0075EA01

1-Stage Heat

208-3

5.6

15.6

19.5

 

20

 

240-3

7.6

18.0

22.6

 

25

 

 

 

1150EA01

 

208-3

11.3

31.2

39.0

 

40

 

240-3

15.0

36.1

45.1

 

50

 

 

 

0100EA01

 

208-3

7.5

20.8

26.0

 

30

 

240-1*

10.0

41.7

52.1

 

60

 

 

240-3

10.0

24.1

30.1

 

35

0150EA01

 

208-3

11.3

31.2

39.0

 

40

 

240-1*

15.0

62.5

78.1

 

80

 

 

240-3

15.0

36.1

45.1

 

50

0200EA01

 

208-3

15.0

41.7

52.1

 

60

048, 060

240-1*

20.0

83.3

104.2

 

110

 

2-Stage Heat

240-3

20.0

46.9

58.6

 

60

0300EA01

 

208-3

22.5

62.5

78.2

 

80

 

240-3

30.0

72.2

90.2

 

100

 

 

 

0300CA01

 

240-1

30.0

124.0

155.0

 

175

0100FA01

 

480-3

10.0

12.0

15.0

 

15

0150FA01

 

480-3

15.0

18.1

22.6

 

25

0200FA01

 

480-3

20.0

24.1

30.1

 

35

0300FA01

 

480-3

30.0

36.1

45.1

 

50

LEGEND

*May be field converted to single-phase units, see electric heat installa-

MCA — Minimum Circuit Ampacity

tion instructions.

MOCP — Maximum Overcurrent Circuit Protection

NOTE: Separate power source is required for all heaters. Control from

(Fuses or Circuit Breaker)

base unit 502A (24 v).