Bryant 524J manual Refrigerant Piping Access Holes

Models: 524J

1 36
Download 36 pages 19.5 Kb
Page 11
Image 11
Fig. 8 - Refrigerant Piping Access Holes

Unit Isolation - Where extremely quiet operation is essential, install isolators between floor and base of unit, or between ceiling and top section of unit.

Be sure that unit is level and adequately supported. Use channels at front and sides of unit for reference points when leveling.

Refrigerant Piping Access - The 524J Series units come with standard knockouts for refrigerant piping. These knockouts are located on both sides of the unit for installation flexibility. The standard knockouts provide sufficient access to the unit’s coils for all 524J*25A, 28A and 30A units. The 524J*25H requires additional holes which must be field-fabricated to accommodate the piping. See Fig. 8 for positions and dimensions for the additional access holes required. Recommended access hole use is also listed for all units. Note that Fig. 8 shows the access holes on the control-box side of the unit; this is the side of the unit with the coil headers, so it is used most often for piping access.

IMPORTANT: Do not bury refrigerant piping underground.

Refrigerant Piping - See Tables 1A–1D for refrigerant pipe connection sizes. For ease in brazing, it is recommended that all internal solder joints be made before unit is placed in final position.

The 524J direct-expansion units have internal factory-installed thermostatic expansion valves (TXVs), distributors, and nozzles for use with R-410A. See Table 2 for part numbers. Knockouts are provided in the unit corner posts for 524J refrigerant piping. See Fig. 8, which also lists recommended knockouts and access holes to use for each 524J unit size. Recommended fittings are listed in Table 3.

The sensor bulb capillary tubes must be routed from the TXVs inside the unit through one of the piping access holes. Clamp the TXV sensor bulb on a vertical portion of the suction line, outside the unit. See Fig. 9.

NOTE: Be sure to remove the styrofoam shipping pad from the TXV. Verify that it has been removed. See Fig. 5.

IMPORTANT: Never attach the sensor to the suction manifold. Do NOT mount the sensor on a trapped portion of the suction line.

The 524J Series evaporator coils have a face-split design. Ensure that lower circuit of coil is first on/last off when connected to the condensing unit and/or system controls. See Fig. 10.

External TXV equalizer connections are provided and factory-brazed into the coil suction manifolds.

If suction line must be horizontal, clamp bulb to suction line at least 45 degrees above bottom, at approximately the 4 o’clock or 8 o’clock position. See Fig.11.

524J

7

 

 

 

6

 

 

 

5

A

B

C

4

 

 

 

 

 

 

3

 

 

 

2

 

 

 

1

 

 

 

C10838

 

USE HOLE

FIELD--FABRICATED HOLE DIAMATERS

FIELD--FABRICATED HOLE POSITION DIMENSIONS

UNIT

 

in. (mm)

 

 

in. (mm)

 

NUMBERS

 

 

 

 

 

 

 

No. 5

No. 6

No. 7

A

B

C

 

 

 

 

 

 

 

 

 

 

524J*25A, 28A, 30A

1,2, 3, 4

 

 

 

 

 

 

 

 

524J*25H

3*, 5, 6, 7

11/8 (28.6)

11/8 (28.6)

13/4 (44.5)

3.25 (82.6)

6.125 (155.6)

10.38 (263.7)

*Must be enlarged from 11/8 in. (28.6mm) to 13/4 in. (44.5mm) NOTE: Access hole knockouts 1--- 4 are factory--- supplied.

Fig. 8 - Refrigerant Piping Access Holes

11

Page 11
Image 11
Bryant 524J manual Refrigerant Piping Access Holes